| 2018-04-26 11:07:51 | FROM: DARIO HERRERO |
| | TO: [email protected], MARTY APPLEBAUM |
| | |
| | DATE: 04/25/2018 07:30 PM |
| | SUBJECT: PERMIT #18010190 |
| | |
| | MR GOMEZ |
| | AS PER OUR LAST CONVERSATION WE HAD SENT YOU THE |
| | ORIGINAL DRAWINGS OF THE UNIT SHOWING THE ELEVATION OF |
| | THE SAME WITH THE HEIGHT RESTRICTION OF 8' INTERIOR |
| | FROM CONCRETE SLAB TO CONCRETE SLAB.? THE ORIGINAL |
| | DESIGN HAS R-11.1 INSULATION ON THE ROOF AND? R-11 ON |
| | THE WALLS.? PER OUR CONVERSATION YOU EXPRESSED THAT THE |
| | EVALUATION SHOULD BE DONE USING THE PERFORMANCE METHOD |
| | FORM R405-2017. ATTACHED IS A COPY OF THE SAME BUT AS I |
| | HAD EXPRESSED TO YOU THE PROGRAM WILL NOT ALLOW AN |
| | INPUT OF LESS THAN R-19 FOR THE ROOF THEREFORE THE |
| | ATTACHED FOR IS WRONG IN THAT THE ROOFING HAS R-19 |
| | INSULATION. |
| | AT THIS POINT WE ARE AT A STANDSTILL.? EVEN THOUGH WE |
| | HAVE A PERMIT CONTINGENT ON THIS ITEM BEING RESOLVED, |
| | WE CANNOT PROCEED DUE TO THE FACT THAT THIS ITEM IS NOT |
| | RESOLVED.? |
| | SINCE THIS IS AN EXISTING UNIT IN A TOWN HOUSE THAT |
| | SHARES THE ROOF WITH 3 OTHER UNITS AND BEING THIS THE |
| | CASE THE UNIT OWNER DOES NOT OWN THE ROOF OR |
| | INSULATION, THE SAME BELONGS TO THE ASSOCIATION, HOW DO |
| | WE PROCEED. |
| | IF WE REFER TO THE 2017 FBC-ENERGY SECTION C501.2 AND |
| | C501.3 |
| | |
| | RESPONSE: |
| | GOOD MORNING MR. HERRERO, |
| | AFTER SOME RESEARCH, I THINK YOU MIGHT BE ABLE TO |
| | COMPLY WITH SEC. 503.1 FBC-ENERGY CONSERVATION (2017) |
| | BY JUST FILING THE EXPOSED CEILING AND WALL CAVITIES |
| | WITH INSULATION. NO NEED TO SUBMIT ENERGY CALCULATIONS. |
| | NOTE: THIS IS ONLY IF THERE IS NO RECONFIGURATION OF |
| | ANY OF THE SPACES IN THE TOWNHOUSE. |
| | I HOPE THIS HELPS, |
| | THANK YOU |
| | |
| | JULIO C. GOMEZ |
| | CITY OF WEST PALM BEACH |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | |
| | |
| | |