| 2018-03-12 11:13:58 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017). |
| | |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | |
| | |
| | |
| | 1- ENERGY CALCULATIONS SUBMITTED PRESCRIPTIVE FORM |
| | R402-2017 SUBMITTED; |
| | A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM AS |
| | REQUIRED BY GENERAL INSTRUCTIONS NOTE#4 OF FORM |
| | SUBMITTED AND SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | B) ITEM #10B DOESN'T COMPLY WITH GENERAL INSTRUCTIONS |
| | NOTE #1. NEED TO COMPLY WITH ALL THE REQUIREMENTS OF |
| | TABLE R402A WHEN USING THE PRESCRIPTIVE METHOD. NEED |
| | R-30 CEILING INSULATION OR USE PERFORMANCE METHOD FORM |
| | 405-2017. |
| | NOTE: ENGINEER WROTE DOWN SEC. R405.2.1. THIS ONLY |
| | APPLIES WHEN USING PERFORMANCE METHOD FORM R405-2017. |
| | |
| | C) COMPLETE TABLE R402B AS REQUIRED BY GENERAL |
| | INSTRUCTIONS NOTE#3. SEC. R101.5.1.1.1 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | D) ENGINEER OF RECORD PREPARING THE ENERGY CALCULATIONS |
| | SUBMITTED TO PROVIDE HIS INFORMATION AS REQUIRED BY |
| | CHAPTER 471 F. S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC |
| | RECORDS. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS. |
| | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| | OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES AS |
| | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. REVISE |
| | VALUATION AS REQUIRED AND INCLUDE THE DESIGN |
| | PROFESSIONAL FEES. |
| | REPEAT COMMENT. |
| | |
| | |
| | NOTE: |
| | PLANS SUBMITTED ARE MISSING ONE MECHANICAL DRAWING M-1. |
| | |
| | |
| | |