| Plan Review Notes For Permit 18010165 |
| Permit Number |
18010165 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-12 06:16:44 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. ON THE FLAT DECK NOA, INDICATE WHICH APPROVED | | | ASSEMBLY IS PROPOSED. ANOTHER DOCUMENT WAS PROVIDED | | | INDICATING ASSEMBLY # 56, BUT IT IS NOT CLEAR WHICH | | | ASSEMBLY THIS IS IN THE PRODUCT APPROVAL. | | | | | | 2. IF THE ASSEMBLY SELECTED DOES NOT MEET THE DESIGN | | | PRESSURES FOR ZONES 2 AND 3, ENGINEERING IS REQUIRED | | | (RAS 117 ENHANCED FASTENING), SEE GENERAL LIMITATION #7 | | | ON THE LAST PAGE OF THE NOA. | | | | | | |
|