Plan Review Notes
Plan Review Notes For Permit 18010130
Permit Number 18010130
Review Stop P
Sequence Number 2
Notes
Date Text
2018-06-07 04:14:191) SHTS.A2.111 & A2.119 - SUBMIT DETAILS FOR THE
 BOLLARDS ADDED AT THE GAS NETER. SHOW TYPE OF MATERIAL
 & DIAMETER, HEIGHT ABOVE GROUND AND EMBEDMENT DEPTH
 INTO GROUND. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT.P2.119.4 - DETAIL #1 - CLUBHOUSE LEVEL - SECTOR
 3A - PROVIDE THE MATCH LINE FOR THE BOTTOM OF THE
 DETAIL ON THE LEFT SIDE WHERE THE 1 INCH CW LINE IS
 SHOWN.WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHTS. P2.121 & P2.122 - IDENTIFY THE PIPE LINES IN
 THE PIPING UTILITY TRAY IN THE CEILING .WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) SHT. P2.122 - THERE ARE A FEW SECTIONS OF PIPE AT
 THE TOP OF THE DRAWING BY THE SEATS THAT GO NOWHERE.
 AREA DRAINS ARE SHOWN WITH NO PIPING TO THEM. IT
 APPEARS AS THOUGH PORTIONS OF THE PLUMBING SYSTEM WERE
 NOT CAPTURED WHEN THE PLANS WERE UPLOADED. CLARIFY.
 5) SHT. P2.128 - THERE IS A DASHED LINE THAT RUNS
 THROUGH THE EXERCISE AREA THAT APPEARS TO BE A GAS LINE
 BUT IT IS NOT IDENTIFIED. IDENTIFY THE LINE AS TO ITS
 USE AND SHOW THE PIPE SIZE. ALSO, REFER TO NUMBERED
 NOTE #5.IT APPEARS THE PIPING TO AND FROM THIS
 REGULATOR HAS NOT BEEN CAPTURED WHEN THE DOCUMENT WAS
 UPLOADED.
 6) PLEASE IDENTIFY THE AREAS AND ROOMS ON THE PLANS
 WITH NAMES AND NUMBERS. THIS WILL HELP EXPEDITE THE
 REVIEW AND ASSIST IN IDENTIFYING THE CHANGES FROM THE
 ORIGINAL PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHT. P4.001 - DETAIL #3 - WATER RISER - IT APPEARS
 THERE ARE SECTIONS OF PIPE MISSING. THERE IS A SECTION
 OF PIPE THAT APPEARS TO BE SANITARY THAT GOES
 NOWHERE.THERE IS NO CLOUD, NO DETAIL NUMBER, NO
 IDENTIFICATION, CLARIFY.
 8) SHT. P.4.001 - DETAIL #3 - THERE APPEARS TO BE
 SECTIONS OF PIPING ON THE WATER RISER MISSING . SUBMIT
 COMPLETE WATER AND SANITARY RISERS FOR REVIEW. IT SEEMS
 AS THOUGH ALL THE IMAGES ARE NOT BEING CAPTURED WHEN
 THE PLANS ARE BEING UPLOADED. WPB AMEND. TO FBC SEC.
 107.2.1.
 9) SHT. P4.001.1 - DETAIL #1 - ASTROS DUGOUT ENLARGED
 PLAN - PROVIDE MATCH LINES FOR THIS DETAIL WPB AMEND.
 TO FBC SEC. 107.2.1.
 10) SHT. P4.003 - SIZE ALL DROP PIPES ENTERING THE FUEL
 TANKS.
 11) SHT. P4.100 - PIPE SIZES ARE MISSING ON THE AREAS
 OF THE WATER AND SANITARY RISER DIAGRAMS.
 12) SHT. P4.101 - PIPE SIZES ARE MISSING ON AREAS OF
 THE SANITARY AND WATER RISERS.
 13) P4.102 - PIPE SIZES ARE MISSING FROM SEVERAL AREAS
 ON THE SANITARY AND WATER RISER DIAGRAMS AND THERE ARE
 SECTIONS OF PIPE THAT ARE MISSING. IT APPEARS AS THOUGH
 NOT EVERYTING IS BEING CAPTURED WHEN THE DRAWINGS ARE
 BING UPLOADED.
 14) P4.103 - PIPE SIZES ARE MISSING FROM THE SANITARY
 AND WATER RISERS. THERE ARE SECTIONS OF PIPE SHOWN ON
 THE SANITARY RISERS THAT GO NOWHERE.
 15) SHT. P4.112 - PIPE SIZES ARE MISSING ON THE WATER
 AND SANITARY RISERS.
 16) SHT. P4.114 - PIPE SIZES ARE MISSING ON THE
 SANITARY AND WATER RISER DIAGRAMS. SIZE THE OVERHEAD
 PIPE LINES IN DETAIL #6.
 17) SHT. P4.116 - PIPE SIZES ARE MISSING ON THE
 SANITARY AND WATER RISERS.
 18) SHT. P4.118 - PIPE SIZES ARE MISSING ON THE
 SANITARY AND WATER RISERS. SUBMIT AN EXPANDED WATER
 RISER FOR DETAIL #3. THE PIPE LINES ARE TOO CLOSE
 TOGETHER TO DO A REVIEW OR TO IDENTIFY THE PIPE.
 19) SHT. P4.119 - SIZE ALL SECTIONS OF THE SANITARY AND
 WATER RISERS.
 20) SHTS. P4.121 & 122 - SIZE ALL SECTIONS OF THE
 SANITARY AND WATER RISER DIGRAMS.SECTIONS OF PIPE ARE
 SHOWN AS GOING NOWHERE.
 21) SHTS. P4.201, P4.202, P4.203 - SIZE ALL SECTIONS OF
 THE WATER AND SANITARY RISERS.
 22) SHTS. P4.205 & P4.206 - SIZE ALL SECTIONS OF THE
 WATER AND SANITARY RISERS.
 23) SHT.P4.210 - SIZE ALL SECTIONS OF THE WATER AND
 SANITARY RISERS. THERE ARE PIPE SECTIONS MISSING
 24) SHTS. P4.300, P4.301, P4.303, P4.304, P4.305,
 P4.306 - THERE ARE PIPE SIZES MISSING ON THE SANITARY
 AND WATER RISERS, THERE ARE SECTIONS OF PIPE MISSING,
 NO CONTINUATION REFERENCE SHEETS ON THE PIPE RISERS.
 25) SHTS. P4.301 THRU P4.307 ARE NOT LISTED INTHE INDEX
 OF DRAWINGS. SUBMIT A NARRATIVE FOR THESE SHEETS
 EXPLAINING THE CHANGES THAT WERE MADE.
 25) SHT.P5.01 - SIZE ALL SECTIONS OF THE WATER AND
 SANITARY RISERS. THERE ARE PIPE SECTIONS MISSING AND
 PLUMBING FIXTURES NOT LABELED.
 26) SHT. P5.101 - GENERAL NOTE #1 STATES THAT WATER
 DISTRIBUTION PIPE SHALL BE STAINLESS STEEL. THIS IS NOT
 WHAT WAS INSTALLED.
 27) SHT. P5.101.1, P5.101.2, P5101.3, P5.101.4, - SIZE
 ALL SECTIONS OF THE WATER RISERS, AND IDENTIFY ALL
 FIXTURES ON THE RISERS. THERE ARE ALSO SECTIONS OF PIPE
 MISSING ON THE RISERS.
 28) SHTS. P5.102 ,1, P5.102.2, P5.103 - SIZE ALL
 SECTIONS OF THE WATER RISERS. THERE ARE ALSO PIPE
 SECTION MISSING AND FIXTURES NOT LABELED .
 29) SHT. P5.402.1. - THE GAS RISER SHOWS AN 1 1/2 GAS
 LINE SERVING 1840 MBH. PER TABLE 402.4 (5) OF THE 2014
 FBC-FUEL GAS, A MAXIMUM OF 1710 MBH CAN BE ON AN 1 1/2
 INCH LINE AT 800 FT. CLARIFY. THERE ARE ALSO PIPE
 SECTIONS MISSING ON THE GAS RISER
 32) SHT. P5.403 - THE BTU LOADS NOTED IN THE CLOUDED
 AREA ON THE PLAN ARE SET OVER OTHER BTU LOADS MAKING
 THE BTU LOAD OF THE APPLIANCES ILLEGIBLE. THIS NEEDS TO
 BE CLEANED UP SO THE PLAN CLEARLY REFLECTS THE BTU
 LOADS OF THE APPLIANCES.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  