| 2018-06-07 04:14:19 | 1) SHTS.A2.111 & A2.119 - SUBMIT DETAILS FOR THE |
| | BOLLARDS ADDED AT THE GAS NETER. SHOW TYPE OF MATERIAL |
| | & DIAMETER, HEIGHT ABOVE GROUND AND EMBEDMENT DEPTH |
| | INTO GROUND. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 2) SHT.P2.119.4 - DETAIL #1 - CLUBHOUSE LEVEL - SECTOR |
| | 3A - PROVIDE THE MATCH LINE FOR THE BOTTOM OF THE |
| | DETAIL ON THE LEFT SIDE WHERE THE 1 INCH CW LINE IS |
| | SHOWN.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) SHTS. P2.121 & P2.122 - IDENTIFY THE PIPE LINES IN |
| | THE PIPING UTILITY TRAY IN THE CEILING .WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 4) SHT. P2.122 - THERE ARE A FEW SECTIONS OF PIPE AT |
| | THE TOP OF THE DRAWING BY THE SEATS THAT GO NOWHERE. |
| | AREA DRAINS ARE SHOWN WITH NO PIPING TO THEM. IT |
| | APPEARS AS THOUGH PORTIONS OF THE PLUMBING SYSTEM WERE |
| | NOT CAPTURED WHEN THE PLANS WERE UPLOADED. CLARIFY. |
| | 5) SHT. P2.128 - THERE IS A DASHED LINE THAT RUNS |
| | THROUGH THE EXERCISE AREA THAT APPEARS TO BE A GAS LINE |
| | BUT IT IS NOT IDENTIFIED. IDENTIFY THE LINE AS TO ITS |
| | USE AND SHOW THE PIPE SIZE. ALSO, REFER TO NUMBERED |
| | NOTE #5.IT APPEARS THE PIPING TO AND FROM THIS |
| | REGULATOR HAS NOT BEEN CAPTURED WHEN THE DOCUMENT WAS |
| | UPLOADED. |
| | 6) PLEASE IDENTIFY THE AREAS AND ROOMS ON THE PLANS |
| | WITH NAMES AND NUMBERS. THIS WILL HELP EXPEDITE THE |
| | REVIEW AND ASSIST IN IDENTIFYING THE CHANGES FROM THE |
| | ORIGINAL PLANS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 7) SHT. P4.001 - DETAIL #3 - WATER RISER - IT APPEARS |
| | THERE ARE SECTIONS OF PIPE MISSING. THERE IS A SECTION |
| | OF PIPE THAT APPEARS TO BE SANITARY THAT GOES |
| | NOWHERE.THERE IS NO CLOUD, NO DETAIL NUMBER, NO |
| | IDENTIFICATION, CLARIFY. |
| | 8) SHT. P.4.001 - DETAIL #3 - THERE APPEARS TO BE |
| | SECTIONS OF PIPING ON THE WATER RISER MISSING . SUBMIT |
| | COMPLETE WATER AND SANITARY RISERS FOR REVIEW. IT SEEMS |
| | AS THOUGH ALL THE IMAGES ARE NOT BEING CAPTURED WHEN |
| | THE PLANS ARE BEING UPLOADED. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 9) SHT. P4.001.1 - DETAIL #1 - ASTROS DUGOUT ENLARGED |
| | PLAN - PROVIDE MATCH LINES FOR THIS DETAIL WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 10) SHT. P4.003 - SIZE ALL DROP PIPES ENTERING THE FUEL |
| | TANKS. |
| | 11) SHT. P4.100 - PIPE SIZES ARE MISSING ON THE AREAS |
| | OF THE WATER AND SANITARY RISER DIAGRAMS. |
| | 12) SHT. P4.101 - PIPE SIZES ARE MISSING ON AREAS OF |
| | THE SANITARY AND WATER RISERS. |
| | 13) P4.102 - PIPE SIZES ARE MISSING FROM SEVERAL AREAS |
| | ON THE SANITARY AND WATER RISER DIAGRAMS AND THERE ARE |
| | SECTIONS OF PIPE THAT ARE MISSING. IT APPEARS AS THOUGH |
| | NOT EVERYTING IS BEING CAPTURED WHEN THE DRAWINGS ARE |
| | BING UPLOADED. |
| | 14) P4.103 - PIPE SIZES ARE MISSING FROM THE SANITARY |
| | AND WATER RISERS. THERE ARE SECTIONS OF PIPE SHOWN ON |
| | THE SANITARY RISERS THAT GO NOWHERE. |
| | 15) SHT. P4.112 - PIPE SIZES ARE MISSING ON THE WATER |
| | AND SANITARY RISERS. |
| | 16) SHT. P4.114 - PIPE SIZES ARE MISSING ON THE |
| | SANITARY AND WATER RISER DIAGRAMS. SIZE THE OVERHEAD |
| | PIPE LINES IN DETAIL #6. |
| | 17) SHT. P4.116 - PIPE SIZES ARE MISSING ON THE |
| | SANITARY AND WATER RISERS. |
| | 18) SHT. P4.118 - PIPE SIZES ARE MISSING ON THE |
| | SANITARY AND WATER RISERS. SUBMIT AN EXPANDED WATER |
| | RISER FOR DETAIL #3. THE PIPE LINES ARE TOO CLOSE |
| | TOGETHER TO DO A REVIEW OR TO IDENTIFY THE PIPE. |
| | 19) SHT. P4.119 - SIZE ALL SECTIONS OF THE SANITARY AND |
| | WATER RISERS. |
| | 20) SHTS. P4.121 & 122 - SIZE ALL SECTIONS OF THE |
| | SANITARY AND WATER RISER DIGRAMS.SECTIONS OF PIPE ARE |
| | SHOWN AS GOING NOWHERE. |
| | 21) SHTS. P4.201, P4.202, P4.203 - SIZE ALL SECTIONS OF |
| | THE WATER AND SANITARY RISERS. |
| | 22) SHTS. P4.205 & P4.206 - SIZE ALL SECTIONS OF THE |
| | WATER AND SANITARY RISERS. |
| | 23) SHT.P4.210 - SIZE ALL SECTIONS OF THE WATER AND |
| | SANITARY RISERS. THERE ARE PIPE SECTIONS MISSING |
| | 24) SHTS. P4.300, P4.301, P4.303, P4.304, P4.305, |
| | P4.306 - THERE ARE PIPE SIZES MISSING ON THE SANITARY |
| | AND WATER RISERS, THERE ARE SECTIONS OF PIPE MISSING, |
| | NO CONTINUATION REFERENCE SHEETS ON THE PIPE RISERS. |
| | 25) SHTS. P4.301 THRU P4.307 ARE NOT LISTED INTHE INDEX |
| | OF DRAWINGS. SUBMIT A NARRATIVE FOR THESE SHEETS |
| | EXPLAINING THE CHANGES THAT WERE MADE. |
| | 25) SHT.P5.01 - SIZE ALL SECTIONS OF THE WATER AND |
| | SANITARY RISERS. THERE ARE PIPE SECTIONS MISSING AND |
| | PLUMBING FIXTURES NOT LABELED. |
| | 26) SHT. P5.101 - GENERAL NOTE #1 STATES THAT WATER |
| | DISTRIBUTION PIPE SHALL BE STAINLESS STEEL. THIS IS NOT |
| | WHAT WAS INSTALLED. |
| | 27) SHT. P5.101.1, P5.101.2, P5101.3, P5.101.4, - SIZE |
| | ALL SECTIONS OF THE WATER RISERS, AND IDENTIFY ALL |
| | FIXTURES ON THE RISERS. THERE ARE ALSO SECTIONS OF PIPE |
| | MISSING ON THE RISERS. |
| | 28) SHTS. P5.102 ,1, P5.102.2, P5.103 - SIZE ALL |
| | SECTIONS OF THE WATER RISERS. THERE ARE ALSO PIPE |
| | SECTION MISSING AND FIXTURES NOT LABELED . |
| | 29) SHT. P5.402.1. - THE GAS RISER SHOWS AN 1 1/2 GAS |
| | LINE SERVING 1840 MBH. PER TABLE 402.4 (5) OF THE 2014 |
| | FBC-FUEL GAS, A MAXIMUM OF 1710 MBH CAN BE ON AN 1 1/2 |
| | INCH LINE AT 800 FT. CLARIFY. THERE ARE ALSO PIPE |
| | SECTIONS MISSING ON THE GAS RISER |
| | 32) SHT. P5.403 - THE BTU LOADS NOTED IN THE CLOUDED |
| | AREA ON THE PLAN ARE SET OVER OTHER BTU LOADS MAKING |
| | THE BTU LOAD OF THE APPLIANCES ILLEGIBLE. THIS NEEDS TO |
| | BE CLEANED UP SO THE PLAN CLEARLY REFLECTS THE BTU |
| | LOADS OF THE APPLIANCES. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | |