| 2018-01-22 12:39:53 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #18010130 |
| | 1/18/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M2.111: FIRE DAMPERS ARE NOT PERMITTED ON THE |
| | HAZARDOUS EXHAUST DUCTS IN THE CHEMICAL AND PAINT |
| | STORAGE ROOMS- SECTION 510.5.7. |
| | |
| | 2) M2.111: PLEASE LABEL ALL ROOMS ON THE PLAN. |
| | |
| | 3) M2.117: PLEASE CLARIFY THE FUNCTION OF THE TWO NEW |
| | CR-A RETURNS IN THE LAUNDRY THAT ARE CONNECTED TO THE |
| | 34X16 TRANSFER DUCT, AND PROVIDE EXHAUST AND AIR |
| | BALANCE CALCULATIONS FOR THE ROOM. |
| | |
| | 4) M2.118: NOTE #19 APPEARS TO INDICATE TRANSFER DUCTS |
| | PROVIDING MAKEUP AIR FROM THE CORRIDOR FOR THE EXHAUST |
| | SYSTEMS. PLEASE SEE SECTION 601.2 EXCEPTION 1 WHICH |
| | PERMITS THE TRANSFERS ONLY IF OUTDOOR AIR IS BEING |
| | SUPPLIED TO THE ROOMS AT A RATE GREATER THAN THAT OF |
| | THE MAKEUP AIR. PLEASE NOTE THIS REVISED PLAN WAS ALSO |
| | SUBMITTED UNDER PERMIT #17040185, AND THE SAME COMMENT |
| | WAS WRITTEN, HOWEVER PER PHONE CONVERSATION WITH EOR |
| | MICHAEL CALAME, THE TRANSFERS WILL BE ELIMINATED AND |
| | REPLACED WITH MAKEUP AIR DUCTS DRAWING AIR DIRECTLY |
| | FROM THE ROOF ABOVE. THIS DECISION WAS BASED ON |
| | INADEQUATE OUTSIDE AIR FROM THE CORRIDOR AND ALSO TO |
| | PREVENT POSSIBLE AIR FROM BEING BACK DRAFTED FROM THE |
| | ROOMS INTO THE CORRIDORS. |
| | |
| | 5) M2.118: PLEASE CLARIFY THE PURPOSE OF THE NEW 30X24 |
| | TRANSFER DUCT AT THE WEIGHT ROOM/OFFICE WALL. |
| | |
| | 6) M2.128: PLEASE SHOW THE DISCHARGE LOCATIONS OF EF |
| | A-2-4. |
| | |
| | 7) M4.02: IT APPEARS THAT VAV-2-7 HAS EITHER BEEN |
| | DELETED OR NOT LABELED ON THE PLAN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |