| Plan Review Notes For Permit 18010130 |
| Permit Number |
18010130 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-09 07:03:44 | 1) SHT. P5.402.1. - THE GAS RISER SHOWS AN 1 1/2 GAS | | | LINE SERVING 1840 MBH. PER TABLE 402.4 (5) OF THE 2014 | | | FBC-FUEL GAS, A MAXIMUM OF 1710 MBH CAN BE ON AN 1 1/2 | | | INCH LINE AT 800 FT. CLARIFY. THERE ARE ALSO PIPE | | | SECTIONS MISSING ON THE GAS RISER | | | 2) SHT. P5.403 - THE BTU LOADS NOTED IN THE CLOUDED | | | AREA ON THE PLAN ARE SET OVER OTHER BTU LOADS MAKING | | | THE BTU LOAD OF THE APPLIANCES ILLEGIBLE. THIS NEEDS TO | | | BE CLEANED UP SO THE PLAN CLEARLY REFLECTS THE BTU | | | LOADS OF THE APPLIANCES. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | |
|