Plan Review Notes For Permit 18010130
Permit Number 18010130
Review Stop G
Sequence Number 1
Notes
Date Text
2018-06-09 07:03:441) SHT. P5.402.1. - THE GAS RISER SHOWS AN 1 1/2 GAS
 LINE SERVING 1840 MBH. PER TABLE 402.4 (5) OF THE 2014
 FBC-FUEL GAS, A MAXIMUM OF 1710 MBH CAN BE ON AN 1 1/2
 INCH LINE AT 800 FT. CLARIFY. THERE ARE ALSO PIPE
 SECTIONS MISSING ON THE GAS RISER
 2) SHT. P5.403 - THE BTU LOADS NOTED IN THE CLOUDED
 AREA ON THE PLAN ARE SET OVER OTHER BTU LOADS MAKING
 THE BTU LOAD OF THE APPLIANCES ILLEGIBLE. THIS NEEDS TO
 BE CLEANED UP SO THE PLAN CLEARLY REFLECTS THE BTU
 LOADS OF THE APPLIANCES.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW