| 2018-01-18 10:42:56 | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| | NFPA 70 2011 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION |
| | FOR PERSONNEL GROUND -FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL SHALL |
| | BE PROVIDED AS REQUIRED IN 210.8(A) THROUGH (D). THE |
| | GROUNDFAULT |
| | CIRCUIT-INTERRUPTER SHALL BE INSTALLED IN A READILY |
| | ACCESSIBLE |
| | LOCATION. |
| | |
| | (B) OTHER THAN DWELLING UNITS. ALL 125-VOLT, |
| | SINGLE-PHASE, |
| | 15- AND 20-AMPERE RECEPTACLES INSTA LLED IN THE |
| | LOCATIONS SPECIFIED |
| | IN 210.8(B)(1) THROUGH (8) SHALL HAVE GROUND-FAULT |
| | CIRCUITINTERRUPTER |
| | PROTECTION FOR PERSONNEL. |
| | (1) BATHROOMS |
| | (2) KITCHENS |
| | (3) ROOFTOPS |
| | (4) OUTDOORS |
| | (5) SINKS ? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 |
| | M (6 FT) OF THE OUTSIDE EDGE OF THE SINK |
| | |
| | (6) INDOOR WET LOCATIONS |
| | (7) LOCKER ROOMS WITH ASSOCIATED SHOWERING FACILITIES |
| | (8) GARAGES, SERVICE BAYS, AND SIMILAR AREAS |
| | |
| | PAGES E2.110, E2.112, E2.113, E2.114, E2.117, E2.118, |
| | E2.119, |
| | |
| | GFCI PROTECTION SEEMS TO BE MISSING IN ALL LOCKER ROOMS |
| | THAT HAVE ASSOCIATED SHOWERS AS STATED IN 210.8(B)(7) |
| | |
| | SEVERAL OTHER AREAS WHERE THERE ARE MOP SINKS OR SOME |
| | OTHER TYPE OF SINK ARE MISSING GFCI PROTECTION IS THOSE |
| | AREAS. |
| | |
| | (E) RECEPTACLES. ALL RECEPTACLES WITHIN 1.83 M (6 FT) |
| | OF A THERAPEUTIC |
| | TUB SHALL BE PROTECTED BY A GROUND-FAULT CIRCUIT |
| | INTERRUPTER. |
| | |
| | PROTECTION, GENERAL. RECEPTACLES RATED 125 VOLTS AND 30 |
| | AMPERES OR LESS AND LOCATED WITHIN 3.0 M (10 FT) OF THE |
| | INSIDE |
| | WALLS OF A SPA OR HO T TUB SHALL BE PROTECTED BY A |
| | GROUND-FAULT |
| | CIRCUIT INTERRUPTER. |
| | |
| | PAGE E4.01 DETAIL #1 |
| | |
| | MAIN SWITCH GEAR ROOM DOES NOT APPEAR TO MEET THE |
| | REQUIREMENTS OF 110.26 (C)(2) FOR WORKING CLEARANCES. |
| | |
| | THIS WILL BE FIELD VERIFIED BY INSPECTIONS. |