Plan Review Notes
Plan Review Notes For Permit 18010127
Permit Number 18010127
Review Stop E
Sequence Number 2
Notes
Date Text
2018-02-07 11:03:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED:
  
 1. NO PLAN REVISIONS ARE INDICATED. REVISIONS SHOULD BE
 CLOUDED OR OTHERWISE OBVIOUS. PLEASE RESUBMIT WITH
 REVISIONS IDENTIFIED. FBC 107.2.1
  
 NEW COMMENT:
  
 2. PLEASE BE ADVISED THAT THIS COMMENT HAS NOT BEEN
 ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF
 IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD
 TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  