Plan Review Notes
Plan Review Notes For Permit 18010127
Permit Number 18010127
Review Stop P
Sequence Number 1
Notes
Date Text
2018-01-10 06:53:2001/10/2018 PLUMBING 1ST REVIEW**DENIED**
  
 1) MIN PLAN REVIEW REQUIRES A SEPERATE SANITARY RISER
 DRAWING. FBC 107.3.5, 107.2.1
  
 2) MIN DIMENSIONS FOR A LAVATORIES IN 15" ON EACH SIDE
 ( TOTAL 30") AND NOT LESS THEN 21" IN FRONT OF FIXTURE.
 FPC P2705.1 (5)
  
 3) MIN SHOWER COMPARTMENTS SHALL NOT BE LESS THEN 30" X
 30" SQUARE, 900 SQUARE INCHES OF INTERIOR DIMENSION
 MIN. EXCEPTION: SHOWER COMPARTMENTS HAVING NOT LESS
 THEN 30" IN MIN DIMENSION SHALL HAVE A CROSS-SECTIONAL
 AREA NO LESS THEN 1300 SQUARE INCHES. FPC P2708.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION