| Plan Review Notes For Permit 18010127 |
| Permit Number |
18010127 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-10 06:53:20 | 01/10/2018 PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) MIN PLAN REVIEW REQUIRES A SEPERATE SANITARY RISER | | | DRAWING. FBC 107.3.5, 107.2.1 | | | | | | 2) MIN DIMENSIONS FOR A LAVATORIES IN 15" ON EACH SIDE | | | ( TOTAL 30") AND NOT LESS THEN 21" IN FRONT OF FIXTURE. | | | FPC P2705.1 (5) | | | | | | 3) MIN SHOWER COMPARTMENTS SHALL NOT BE LESS THEN 30" X | | | 30" SQUARE, 900 SQUARE INCHES OF INTERIOR DIMENSION | | | MIN. EXCEPTION: SHOWER COMPARTMENTS HAVING NOT LESS | | | THEN 30" IN MIN DIMENSION SHALL HAVE A CROSS-SECTIONAL | | | AREA NO LESS THEN 1300 SQUARE INCHES. FPC P2708.1 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|