| 2018-01-22 07:22:13 | POOL: |
| | 1) SUBMIT A COPY OF THE APPLICATION FOR THE OPERATING |
| | PERMIT FROM THE DEPARTMENT OF HEALTH PER FL. STATUTES |
| | 541.03. |
| | 2) SHOW THE WIDTH OF THE POOL. THE LENGTH OF THE POOL |
| | IS SHOWN ON PAGE 1 BUT I CANNOT FIND THE WIDTH. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 3) SHOW THE SPACING OF THE FLOOR INLETS TO ADJACENT |
| | WALLS. COMPLY WITH FBC SEC 454.1.6.5.9.3 OR SEC. |
| | 454.1.6.5.9.4. |
| | 4) PAGE 3 OF 4 - THE VACUUM LINE DETAIL NOTES THE |
| | VACUUM LINE TO BE LOCATED A MINIMUM OF 12 INCHES AND A |
| | MAXIMUM OF 15 INCHES BELOW THE WATER LINE AND THE WALL |
| | SECTION DETAIL SHOWS THE VACUUM LINE A MAXIMUM OF 12 |
| | INCHES BELOW THE WATER LINE. CLARIFY. |
| | 5) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE MAIN DRAIN. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 6) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PUMP AND ALSO FOR THE CARTRIDGE |
| | FILTERS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | |
| | SPA: |
| | 7) SUBMIT A COPY OF THE APPLICATION FOR THE OPERATING |
| | PERMIT FROM THE DEPARTMENT OF HEALTH PER FL. STATUTES |
| | 541.03. |
| | 8) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE MAIN DRAIN. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 9) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PUMP AND ALSO FOR THE CARTRIDGE |
| | FILTERS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE POOL HEATER.WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |