2018-01-22 07:22:13POOL:
 1) SUBMIT A COPY OF THE APPLICATION FOR THE OPERATING
 PERMIT FROM THE DEPARTMENT OF HEALTH PER FL. STATUTES
 541.03.
 2) SHOW THE WIDTH OF THE POOL. THE LENGTH OF THE POOL
 IS SHOWN ON PAGE 1 BUT I CANNOT FIND THE WIDTH. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) SHOW THE SPACING OF THE FLOOR INLETS TO ADJACENT
 WALLS. COMPLY WITH FBC SEC 454.1.6.5.9.3 OR SEC.
 454.1.6.5.9.4.
 4) PAGE 3 OF 4 - THE VACUUM LINE DETAIL NOTES THE
 VACUUM LINE TO BE LOCATED A MINIMUM OF 12 INCHES AND A
 MAXIMUM OF 15 INCHES BELOW THE WATER LINE AND THE WALL
 SECTION DETAIL SHOWS THE VACUUM LINE A MAXIMUM OF 12
 INCHES BELOW THE WATER LINE. CLARIFY.
 5) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE MAIN DRAIN. WPB AMEND. TO FBC
 SEC. 107.2.1.
 6) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PUMP AND ALSO FOR THE CARTRIDGE
 FILTERS. WPB AMEND. TO FBC SEC. 107.2.1.
  
  
 SPA:
 7) SUBMIT A COPY OF THE APPLICATION FOR THE OPERATING
 PERMIT FROM THE DEPARTMENT OF HEALTH PER FL. STATUTES
 541.03.
 8) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE MAIN DRAIN. WPB AMEND. TO FBC
 SEC. 107.2.1.
 9) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PUMP AND ALSO FOR THE CARTRIDGE
 FILTERS. WPB AMEND. TO FBC SEC. 107.2.1.
 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE POOL HEATER.WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW