| Plan Review Notes For Permit 18010083 |
| Permit Number |
18010083 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-18 11:44:45 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT A COPY OF THE PUBLIC SWIMMING POOL OPERATING | | | PERMIT APPLICATION FROM THE PALM BEACH COUNTY HEALTH | | | DEPARTMENT AS REQUIRED BY FLORIDA STATUTE 514.03. | | | | | | 2) FBC 454.1.2.4 COLOR. THE INTERIOR FINISH COATING | | | FLOORS AND WALLS SHALL BE COMPRISED OF A NONPIGMENTED | | | WHITE CEMENTITIOUS BINDER COMPONENT TOGETHER WITH A | | | SAND/AGGREGATE COMPONENT. THE FINISH COATING SHALL HAVE | | | A DRY LIGHTNESS LEVEL (CIE L VALUE) OF 80.0 OR GREATER | | | AND A WET LUMINOUS REFLECTANCE VALUE (CIE Y VALUE) OF | | | 50.0 OR GREATER, AS DETERMINED BY TEST RESULTS PROVIDED | | | BY THE MANUFACTURER, UTILIZING TESTING METHODOLOGY FROM | | | AMERICAN STANDARD ASTM D4086, ASTM E1477, ASTM E1347. | | | | | | 3) ADDRESS OTHER REVIEWER'S COMMENTS. | | | |
|