2018-01-18 11:44:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A COPY OF THE PUBLIC SWIMMING POOL OPERATING
 PERMIT APPLICATION FROM THE PALM BEACH COUNTY HEALTH
 DEPARTMENT AS REQUIRED BY FLORIDA STATUTE 514.03.
  
 2) FBC 454.1.2.4 COLOR. THE INTERIOR FINISH COATING
 FLOORS AND WALLS SHALL BE COMPRISED OF A NONPIGMENTED
 WHITE CEMENTITIOUS BINDER COMPONENT TOGETHER WITH A
 SAND/AGGREGATE COMPONENT. THE FINISH COATING SHALL HAVE
 A DRY LIGHTNESS LEVEL (CIE L VALUE) OF 80.0 OR GREATER
 AND A WET LUMINOUS REFLECTANCE VALUE (CIE Y VALUE) OF
 50.0 OR GREATER, AS DETERMINED BY TEST RESULTS PROVIDED
 BY THE MANUFACTURER, UTILIZING TESTING METHODOLOGY FROM
 AMERICAN STANDARD ASTM D4086, ASTM E1477, ASTM E1347.
  
 3) ADDRESS OTHER REVIEWER'S COMMENTS.
  