Plan Review Notes
Plan Review Notes For Permit 18010035
Permit Number 18010035
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-11 07:51:40PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ACCORDING TO THE FBC EXISTING BUILDING, THIS PROJECT
 IS CONSIDERED A LEVEL 3 ALTERATION. SPECIFY THE LEVEL
 OF ALTERATION ON THE PLANS. FBC EXISTING BUILDING
 SECTION 505
  
 2) THE PROPOSED FLOOR PLANS THAT WERE SUBMITTED SHOW
 CHANGES TO THE EXTERIOR DOORS AND WINDOWS OF THE
 STRUCTURE. PROVIDE A COMPLETE SCOPE OF WORK ON THE
 PLANS. FBC 107.2.1
  
 3) PROVIDE WINDOW AND DOOR SCHEDULES WITH SIZES ON THE
 PLANS. FBC 107.2.1
  
 4) PROVIDE A TYPICAL FRAMING DETAIL FOR THE NEW
 EXTERIOR WINDOW AND DOOR OPENINGS. PROVIDE HEADER AND
 STRAPPING DETAILS AND OTHER PERTINENT INFORMATION.
 FBC-R601.2
  
 5) PROVIDE A DETAIL SHOWING HOW THE OPENINGS IN THE
 EXTERIOR WALLS WILL BE INFILL-ED. INCLUDING INSULATION,
 INTERIOR AND EXTERIOR WALL COVERINGS. FBC-R702 AND R703
  
 6) SPECIFY THE WIND DESIGN DATA ON THE PLANS.
 FBC-R301.2.1
  
 7) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 EXTERIOR WINDOW AND DOOR OPENINGS ON THE PLANS.
 FBC-R301.2.1
  
 8) SHOW COMPLIANCE WITH FBC-R310.1 EMERGENCY ESCAPE AND
 RESCUE REQUIRED. BASEMENTS, HABITABLE ATTICS AND EVERY
 SLEEPING ROOM SHALL HAVE AT LEAST ONE OPERABLE
 EMERGENCY ESCAPE AND RESCUE OPENING.
  
 9) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 10) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE EXTERIOR DOORS AND
 WINDOWS.
  
 11) FBC - R301.2.1.2 PROTECTION OF OPENINGS. GLAZED
 OPENINGS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS
 REGIONS SHALL BE PROTECTED FROM WINDBORNE DEBRIS.
 GLAZED OPENING PROTECTION FOR WINDBORNE DEBRIS SHALL
 MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST OF ASTM
 E 1996 AND ASTM E 1886 REFERENCED THEREIN, SSTD 12, TAS
 201, 202 AND 203 OR AAMA 506, AS APPLICABLE. IF STORM
 PANELS WILL BE USED TO COMPLY WITH LARGE MISSILE IMPACT
 PROTECTION, SUBMIT TWO SETS OF PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  