2018-08-01 16:23:565TH REVIEW FBC-2007 MECHANICAL
 PERMIT #18010014
 8/1/2018
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-100 & M-101: THE REVISED PLAN NOW INDICATES
 HP-F IS SUPPLYING 1350 CFMS OF SUPPLY AIR WHICH IS
 STILL 250 CFMS SHORT OF THE UNIT'S CAPACITY OF 1600
 CFMS PER THE EQUIPMENT SCHEDULE. THIS UNIT STILL
 APPEARS TO BE OVERSIZED FOR THE AREA IT IS SERVING.
 PLEASE PROVIDE AC COOLING AND HEATING CALCULATIONS
 SPECIFIC TO THE AREA THIS UNIT IS SERVING- SECTION
 503.2.2 FBC-10 ENERGY
 CONSERVATION.
  
 2) THE REVISED SHEETS M-100 & M-101 MUST BE
 ELECTRONICALLY SIGNED AND SEALED BY THE EOR- SECTION
 61G15-23.005 FLORIDA ADMININSTRATIVE CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  