| Plan Review Notes For Permit 18010014 |
| Permit Number |
18010014 |
|
| Review Stop |
M |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2018-08-01 16:23:56 | 5TH REVIEW FBC-2007 MECHANICAL | | | PERMIT #18010014 | | | 8/1/2018 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-100 & M-101: THE REVISED PLAN NOW INDICATES | | | HP-F IS SUPPLYING 1350 CFMS OF SUPPLY AIR WHICH IS | | | STILL 250 CFMS SHORT OF THE UNIT'S CAPACITY OF 1600 | | | CFMS PER THE EQUIPMENT SCHEDULE. THIS UNIT STILL | | | APPEARS TO BE OVERSIZED FOR THE AREA IT IS SERVING. | | | PLEASE PROVIDE AC COOLING AND HEATING CALCULATIONS | | | SPECIFIC TO THE AREA THIS UNIT IS SERVING- SECTION | | | 503.2.2 FBC-10 ENERGY | | | CONSERVATION. | | | | | | 2) THE REVISED SHEETS M-100 & M-101 MUST BE | | | ELECTRONICALLY SIGNED AND SEALED BY THE EOR- SECTION | | | 61G15-23.005 FLORIDA ADMININSTRATIVE CODE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|