| Plan Review Notes For Permit 18010014 |
| Permit Number |
18010014 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2018-07-30 17:40:20 | 4TH REVIEW FBC-2017 MECHANICAL | | | PERMIT #18010014 | | | 4/2518 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M100 & M101: HP-F APPEARS TO BE OVERSIZED AT | | | 4-TONS AND 1600 CFMS OF SUPPLY AIR BECAUSE THE LAYOUT | | | PLAN INDICATES IT IS ONLY REQUIRED TO PRODUCE 1000 CFMS | | | WHICH WOULD BE MORE TYPICAL OF A 2.5 TON SYSTEM- PLEASE | | | CLARIFY. | | | | | | 2) IT HAS BEEN DETERMINED THAT ALL APARTMENT BUILDOUTS | | | WILL BE DESIGNED UNDER THE 2010 FLORIDA BUILDING CODES | | | UNTIL WHICH TIME THE BUILDING RECEIVES A CERTIFICATE OF | | | OCCUPANCY. PLEASE CORRECT THE 2014 REFERENCE ON THE A-1 | | | COVER SHEET. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|