2018-07-30 17:40:204TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18010014
 4/2518
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M100 & M101: HP-F APPEARS TO BE OVERSIZED AT
 4-TONS AND 1600 CFMS OF SUPPLY AIR BECAUSE THE LAYOUT
 PLAN INDICATES IT IS ONLY REQUIRED TO PRODUCE 1000 CFMS
 WHICH WOULD BE MORE TYPICAL OF A 2.5 TON SYSTEM- PLEASE
 CLARIFY.
  
 2) IT HAS BEEN DETERMINED THAT ALL APARTMENT BUILDOUTS
 WILL BE DESIGNED UNDER THE 2010 FLORIDA BUILDING CODES
 UNTIL WHICH TIME THE BUILDING RECEIVES A CERTIFICATE OF
 OCCUPANCY. PLEASE CORRECT THE 2014 REFERENCE ON THE A-1
 COVER SHEET.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  