Plan Review Notes
Plan Review Notes For Permit 18010014
Permit Number 18010014
Review Stop M
Sequence Number 4
Notes
Date Text
2018-06-08 10:00:323RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18010014
 4/2518
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS THE 4TH REQUEST FOR ENERGY CALCULATIONS FOR
 THE APARTMENT BUILDOUT. SUBMITTED FOR THIS REVIEW IS A
 COVER SHEET FROM THE EOR STANTEC WHICH IS TITLED
 "ENERGY COMPLIANCE CALCULATIONS FOR THE BRISTOL ". THE
 COVER SHEET DOES NOT SPECIFICALLY REFERENCE THE
 APARTMENT, AND THERE IS NO COMPLIANCE DATA TO GO WITH
 THE SHEET, EXCEPT UPLOADED FOR REVIEW IS THE ORIGNAL
 2010 ENERGY GAUGE COMPLIANCE SUBMITTAL FOR THE ENTIRE
 BUILDING. PLEASE NOTE THE NEW APARTMENT BUILDOUT IS
 UNDER THE 2017 CODE, THEREFORE REVISED CALCULATIONS
 SPECIFIC TO THE APARTMENT MUST BE SUBMITTED.
  
 2) COMMENT #8 FROM THE PREVIOUS REVIEW ABOUT THE
 MISSING FIRE DAMPERS FOR THE 6" FLEX DUCT AND THE O/A
 DUCT PENETRATING THE LAUNDRY ROOM WALL STILL EXISTS.
 PLEASE REMOVE THE FIRE-RATED WALL SYMBOL AT THE
 PENETRATIONS IF THE WALL IS NOT RATED, OR PROVIDE THE
 DAMPERS.
  
 3) M.100: AS PREVIOUSLY REQUESTED, A SMOKE DETECTOR IS
 REQUIRED IN THE SUPPLY TRUNK OF HP-G PER SECTION
 606.2.1.
  
 4) M.100: ACKNOWLEDGED THAT MANUFACTURER'S
 SPECIFICATIONS FOR THE GAS RANGE, KITCHEN EXHAUST HOOD
 AND DUCT, AND THE DRYER WILL BE DEFERRED SUBMITTALS.L
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  