| 2018-06-08 10:00:32 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18010014 |
| | 4/2518 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS IS THE 4TH REQUEST FOR ENERGY CALCULATIONS FOR |
| | THE APARTMENT BUILDOUT. SUBMITTED FOR THIS REVIEW IS A |
| | COVER SHEET FROM THE EOR STANTEC WHICH IS TITLED |
| | "ENERGY COMPLIANCE CALCULATIONS FOR THE BRISTOL ". THE |
| | COVER SHEET DOES NOT SPECIFICALLY REFERENCE THE |
| | APARTMENT, AND THERE IS NO COMPLIANCE DATA TO GO WITH |
| | THE SHEET, EXCEPT UPLOADED FOR REVIEW IS THE ORIGNAL |
| | 2010 ENERGY GAUGE COMPLIANCE SUBMITTAL FOR THE ENTIRE |
| | BUILDING. PLEASE NOTE THE NEW APARTMENT BUILDOUT IS |
| | UNDER THE 2017 CODE, THEREFORE REVISED CALCULATIONS |
| | SPECIFIC TO THE APARTMENT MUST BE SUBMITTED. |
| | |
| | 2) COMMENT #8 FROM THE PREVIOUS REVIEW ABOUT THE |
| | MISSING FIRE DAMPERS FOR THE 6" FLEX DUCT AND THE O/A |
| | DUCT PENETRATING THE LAUNDRY ROOM WALL STILL EXISTS. |
| | PLEASE REMOVE THE FIRE-RATED WALL SYMBOL AT THE |
| | PENETRATIONS IF THE WALL IS NOT RATED, OR PROVIDE THE |
| | DAMPERS. |
| | |
| | 3) M.100: AS PREVIOUSLY REQUESTED, A SMOKE DETECTOR IS |
| | REQUIRED IN THE SUPPLY TRUNK OF HP-G PER SECTION |
| | 606.2.1. |
| | |
| | 4) M.100: ACKNOWLEDGED THAT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE GAS RANGE, KITCHEN EXHAUST HOOD |
| | AND DUCT, AND THE DRYER WILL BE DEFERRED SUBMITTALS.L |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |