2018-04-21 09:18:37PLUMBING PROVISO:
  
 3. REINFORCEMENT FOR GRAB BARS IS REQUIRED IN ALL THE
 BATHROOM LOCATED IN DWELLING UNIT PLEASE PROVIDE
 DETAILS SHOWING MOUNTING HEIGHTS OF GRAB BAR BACKING.
 PER FHA DESIGN MANUAL REQUIREMENT #6
  
 4. SHT. A-4 DETAIL #4 THE WATER PROOF MEMBRANE FOR THE
 SHOWER PAN SHALL BE SLOPED TO THE DRAIN MIN OF 2% SLOPE
 .PER FBC PL 417.5.2 THE WATER PROF MEMBRANE IS SHOWN AS
 FLAT ON THE CONCRETE SLAB. THE WATER PROOF MEMBRANE
 SHALL BE SLOPED NOT JUST THE TILE.
  