| Date |
Text |
| 2018-04-25 10:56:07 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18010014 |
| | 4/2518 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE 1ST AND 2ND REVIEW COMMENTS HAVE BEEN PARTIALLY |
| | ADDRESSED. COMMENTS, OR PARTS OF COMMENTS REMAINING ARE |
| | LISTED BELOW IN THEIR ORIGINAL NUMERICAL ORDER. |
| | |
| | 1) THE REQUESTED AC CALCULATIONS WERE NOT PROVIDED. |
| | |
| | 2) THE REQUESTED ENERGY CALCULATIONS WERE NOT PROVIDED. |
| | |
| | 3) INDICATE HOW OUTSIDE AIR IS BEING SUPPLIED TO THE |
| | HEAT PUMPS PER TABLE 403.3, AND HOW THE O/A SUPPLY WILL |
| | BE AUTOMATICALLY DAMPERED PER SECTION C403.2.4.3 FBC-17 |
| | ENERGY CONSERVATION. |
| | |
| | 4) SHEET M1.00: THERE IS NO TEXT ON THE PLAN FOR KEYED |
| | NOTES #1 & 2. |
| | |
| | 5) M1.00 & A-4: NON-COMBUSTIBLE DOORS ARE REQUIRED FOR |
| | THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2 FBC-17 |
| | MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY CONSERVATION. |
| | (NOT PROVIDED) |
| | |
| | 6) M1.00: PROVIDE A SECTION CUT OF THE COVE RETURNS |
| | THAT SHOWS THE DIMENSIONS OF THE OPENING, AND WHAT |
| | CONSTRUCTION MATERIALS WILL BE USED- SECTION 602.2. |
| | (NOT PROVIDED) |
| | |
| | 7) M.100: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GAS RANGE, EXHAUST HOOD, AND EXHAUST DUCT, AND THE |
| | DRYER. (NOT PROVIDED). |
| | |
| | 8) M.100: IT APPEARS THAT FIRE DAMPERS ARE MISSING |
| | WHERE THE 6" FLEX DUCT AND O/A DUCT ARE PENETRATING THE |
| | CORE WALL SEPARATING THE HALL AND THE LAUNDRY- SECTION |
| | 607.5.2. |
| | |
| | 9) M102.02: PLEASE INDICATE WHICH OF THE SUBDUCT |
| | DETAILS APPLIES TO THE DRYER EXHAUST, THE TOILET |
| | EXHAUST, AND THE RANGE EXHAUST. (NOT PROVIDED). |
| | |
| | 10) M.100: A SMOKE DETECTOR IS REQUIRED IN THE SUPPLY |
| | TRUNK OF HP-G PER SECTION 606.2.1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |