Plan Review Notes
Plan Review Notes For Permit 18010014
Permit Number 18010014
Review Stop P
Sequence Number 2
Notes
Date Text
2018-03-26 11:39:312ND REVIEW: FBC 2010
  
 PLUMBING COMMENTS: A COMMENT RESPONSE LETTER FOR
 PLUMBING WAS NOT PROVIDED, TO EXPEDITE APPROVAL PLEASE
 PROVIDE RESPONSE LETTER AND CONTACT PLAN REVIEWER.
  
 PREVIOUS COMMENTS NOT COMPLIED WITH.
  
 2. PLEASE INDICATE ON THE PLAN THE SAFE HARBOR DESIGN
 DOCUMENT THAT WAS USED TO DESIGN THIS UNIT TO THE FHA
 REQUIREMENTS. WPB AMEND TO FBC 107.2.1
  
 3. REINFORCEMENT FOR GRAB BARS IS REQUIRED IN ALL THE
 BATHROOM LOCATED IN DWELLING UNIT PLEASE PROVIDE
 DETAILS SHOWING MOUNTING HEIGHTS AND LOCATION OF GRAB
 BAR BACKING. PER FHA DESIGN MANUAL REQUIREMENT #6
  
 4. SHT. A-4 DETAIL #4 THE WATER PROOF MEMBRANE FOR THE
 SHOWER PAN SHALL BE SLOPED TO THE DRAIN MIN OF 2% SLOPE
 .PER FBC PL 417.5.2
  
 5. PLEASE PROVIDE MANUFACTURE SPECIFICATION AND
 INSTALLATION GUIDE FOR THE WATER PROOF MEMBRANE FOR
 SHOWER LINER SHALL COMPLY WITH FBC PL 417.5.2.5
  
 6. PROVIDE DETAIL FOR HEIGHT OF LAVATORY SANITARY TO
 COMPLY WITH FHA
  
 7. SHT. P001.00 THIS PROJECT IS DESIGNED UNDER FBC 2010
 UNDER THE BUILDING DEPARTMENT NOTES IT LIST 2014. THE
 GAS SHALL COMPLY WITH FBC FG 2010 PLEASE CLARIFY PER
 WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  