2018-03-21 17:59:282ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18010014
 3/21/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE 1ST REVIEW COMMENTS WERE NOT ADDRESSED AND THE
 REQUESTED RESPONSE LETTER FROM THE DESIGN PROFESSIONAL
 WAS NOT PROVIDED. PLEASE NOTE THAT IT IS ACKNOWLEDGED
 THAT ENERGY, AC, AND VENTILATION CALCULATIONS WERE
 SUBMITTED FOR THE APARTMENT UNDER THE MAIN PERMITS FOR
 THE BRISTOL, HOWEVER THIS IS A SEPARATE PERMIT TO BE
 FILED FOR THE PUBLIC RECORD, AND THEREFORE IT IS
 NECESSARY
  
 THAT ALL COMPLIANCES SPECIFICALLY FOR THIS UNIT
 BUILD-OUT ARE MET. I HAVE COPIED MY 1ST REVIEW
 COMMENTS, INCLUDING THE REQUEST FOR THE CALCULATIONS
 BELOW- PLEASE COMPLY:
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 HEAT PUMPS- SECTION C403.2.1 FBC-17 ENERGY
 CONSERVATION.
  
 2) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTION C101.5
  
 3) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 SPACE IN ACCORDANCE WITH TABLE 403.1.1, AND INDICATE
 HOW THE OUTDOOR AIR FLOW WILL BE AUTOMATICALLY
 CONTROLLED- SEE SECTION C403.2.4.3 FBC-17 ENERGY
 CONSERVATION.
  
 4) M1.00: CLARIFY HOW SUPPLY AIR IS BEING RETURNED INTO
 THE AC CLOSETS- SECTION 601.6.
  
 5) M1.00 & A-4: NON-COMBUSTIBLE DOORS ARE REQUIRED FOR
 THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2 FBC-17
 MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY CONSERVATION.
  
 6) M1.00: PROVIDE A SECTION CUT OF THE COVE RETURNS
 THAT SHOWS THE DIMENSIONS OF THE OPENING, AND WHAT
 CONSTRUCTION MATERIALS WILL BE USED- SECTION 602.2
  
 7) M.100: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS RANGE, EXHAUST HOOD, AND EXHAUST DUCT, AND THE
 DRYER.
  
 8) M.100: IT APPEARS THAT FIRE DAMPERS ARE MISSING
 WHERE THE 6" FLEX DUCT AND O/A DUCT ARE PENETRATING THE
 CORE WALL SEPARATING THE HALL AND THE LAUNDRY- SECTION
 607.5.2.
  
 9) M102.02: PLEASE INDICATE WHICH OF THE SUBDUCT
 DETAILS APPLIES TO THE DRYER EXHAUST, THE TOILET
 EXHAUST, AND THE RANGE EXHAUST.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER