| Date |
Text |
| 2018-03-21 17:59:28 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18010014 |
| | 3/21/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE 1ST REVIEW COMMENTS WERE NOT ADDRESSED AND THE |
| | REQUESTED RESPONSE LETTER FROM THE DESIGN PROFESSIONAL |
| | WAS NOT PROVIDED. PLEASE NOTE THAT IT IS ACKNOWLEDGED |
| | THAT ENERGY, AC, AND VENTILATION CALCULATIONS WERE |
| | SUBMITTED FOR THE APARTMENT UNDER THE MAIN PERMITS FOR |
| | THE BRISTOL, HOWEVER THIS IS A SEPARATE PERMIT TO BE |
| | FILED FOR THE PUBLIC RECORD, AND THEREFORE IT IS |
| | NECESSARY |
| | |
| | THAT ALL COMPLIANCES SPECIFICALLY FOR THIS UNIT |
| | BUILD-OUT ARE MET. I HAVE COPIED MY 1ST REVIEW |
| | COMMENTS, INCLUDING THE REQUEST FOR THE CALCULATIONS |
| | BELOW- PLEASE COMPLY: |
| | |
| | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | HEAT PUMPS- SECTION C403.2.1 FBC-17 ENERGY |
| | CONSERVATION. |
| | |
| | 2) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTION C101.5 |
| | |
| | 3) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE |
| | SPACE IN ACCORDANCE WITH TABLE 403.1.1, AND INDICATE |
| | HOW THE OUTDOOR AIR FLOW WILL BE AUTOMATICALLY |
| | CONTROLLED- SEE SECTION C403.2.4.3 FBC-17 ENERGY |
| | CONSERVATION. |
| | |
| | 4) M1.00: CLARIFY HOW SUPPLY AIR IS BEING RETURNED INTO |
| | THE AC CLOSETS- SECTION 601.6. |
| | |
| | 5) M1.00 & A-4: NON-COMBUSTIBLE DOORS ARE REQUIRED FOR |
| | THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2 FBC-17 |
| | MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY CONSERVATION. |
| | |
| | 6) M1.00: PROVIDE A SECTION CUT OF THE COVE RETURNS |
| | THAT SHOWS THE DIMENSIONS OF THE OPENING, AND WHAT |
| | CONSTRUCTION MATERIALS WILL BE USED- SECTION 602.2 |
| | |
| | 7) M.100: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GAS RANGE, EXHAUST HOOD, AND EXHAUST DUCT, AND THE |
| | DRYER. |
| | |
| | 8) M.100: IT APPEARS THAT FIRE DAMPERS ARE MISSING |
| | WHERE THE 6" FLEX DUCT AND O/A DUCT ARE PENETRATING THE |
| | CORE WALL SEPARATING THE HALL AND THE LAUNDRY- SECTION |
| | 607.5.2. |
| | |
| | 9) M102.02: PLEASE INDICATE WHICH OF THE SUBDUCT |
| | DETAILS APPLIES TO THE DRYER EXHAUST, THE TOILET |
| | EXHAUST, AND THE RANGE EXHAUST. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |