| 2018-03-08 07:00:04 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18010014 |
| | ADD: 1100 S. FLAGLER DR. SUITE; 12A |
| | CONT: PDC DEVELOPMENT CORP. |
| | TEL: 561-793-5852 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: THURS. MARCH 08/2018 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) SHEET 002-A-2 INDICATES THE USE OF TILE, MARBLE, BUT |
| | THERE HAS BEEN NO SUBMISSION FOR CODE COMPLIANCE FOR |
| | TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED |
| | TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 1A) COMPLIED. FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) PROVISO/ DEFERRED SUBMITTAL: FBC-B 2014 1207.2 |
| | AIR-BORNE SOUND.WALLS, PARTITIONS AND FLOOR/CEILING |
| | ASSEMBLIES SEPARATING DWELLING UNITS FROM EACH OTHER OR |
| | FROM PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND |
| | TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 IF |
| | FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. |
| | |
| | 2C) PROVISO / DEFERRED SUBMITTAL: FLAME SPREAD- FBC-B |
| | 2014 603.1. EXCEPTION 2. INSULATION INSTALLED BETWEEN A |
| | FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |