Plan Review Notes
Plan Review Notes For Permit 18010014
Permit Number 18010014
Review Stop M
Sequence Number 1
Notes
Date Text
2018-02-16 11:06:031ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18010014
 2/16/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 HEAT PUMPS- SECTION C403.2.1 FBC-17 ENERGY
 CONSERVATION.
  
 2) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTION C101.5
  
 3) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 SPACE IN ACCORDANCE WITH TABLE 403.1.1, AND INDICATE
 HOW THE OUTDOOR AIR FLOW WILL BE AUTOMATICALLY
 CONTROLLED- SEE SECTION C403.2.4.3 FBC-17 ENERGY
 CONSERVATION.
  
 4) M1.00: CLARIFY HOW SUPPLY AIR IS BEING RETURNED INTO
 THE AC CLOSETS- SECTION 601.6.
  
 5) M1.00 & A-4: NON-COMBUSTIBLE DOORS ARE REQUIRED FOR
 THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2 FBC-17
 MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY CONSERVATION.
  
 6) M1.00: PROVIDE A SECTION CUT OF THE COVE RETURNS
 THAT SHOWS THE DIMENSIONS OF THE OPENING, AND WHAT
 CONSTRUCTION MATERIALS WILL BE USED- SECTION 602.2
  
 7) M.100: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS RANGE, EXHAUST HOOD, AND EXHAUST DUCT. PROVIDE A
 DETAIL SHOWING THE CONNECTION OF THE EXHAUST DUCT INTO
 THE SHAFT.
  
 8) M1.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 DRYER, AND PROVIDE A DETAIL SHOWING THE CONNECTION OF
 THE EXHAUST DUCT INTO THE SHAFT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  