| 2018-02-16 11:06:03 | 1ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION |
| | CODES |
| | PERMIT #18010014 |
| | 2/16/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | HEAT PUMPS- SECTION C403.2.1 FBC-17 ENERGY |
| | CONSERVATION. |
| | |
| | 2) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTION C101.5 |
| | |
| | 3) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE |
| | SPACE IN ACCORDANCE WITH TABLE 403.1.1, AND INDICATE |
| | HOW THE OUTDOOR AIR FLOW WILL BE AUTOMATICALLY |
| | CONTROLLED- SEE SECTION C403.2.4.3 FBC-17 ENERGY |
| | CONSERVATION. |
| | |
| | 4) M1.00: CLARIFY HOW SUPPLY AIR IS BEING RETURNED INTO |
| | THE AC CLOSETS- SECTION 601.6. |
| | |
| | 5) M1.00 & A-4: NON-COMBUSTIBLE DOORS ARE REQUIRED FOR |
| | THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2 FBC-17 |
| | MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY CONSERVATION. |
| | |
| | 6) M1.00: PROVIDE A SECTION CUT OF THE COVE RETURNS |
| | THAT SHOWS THE DIMENSIONS OF THE OPENING, AND WHAT |
| | CONSTRUCTION MATERIALS WILL BE USED- SECTION 602.2 |
| | |
| | 7) M.100: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GAS RANGE, EXHAUST HOOD, AND EXHAUST DUCT. PROVIDE A |
| | DETAIL SHOWING THE CONNECTION OF THE EXHAUST DUCT INTO |
| | THE SHAFT. |
| | |
| | 8) M1.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | DRYER, AND PROVIDE A DETAIL SHOWING THE CONNECTION OF |
| | THE EXHAUST DUCT INTO THE SHAFT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |