| 2018-01-03 09:40:22 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. FBC 107, SCOPE NOT CLEAR. THERE IS ALREADY A DENIED |
| | ROOF PERMIT APPLICATION FOR THIS PROPERTY. APPLICANT |
| | HAS THREE OPTIONS: |
| | |
| | OPTION A: IF ROOF DAMAGE IS LESS THAN 25% OF THE ROOF, |
| | AS DETERMINED BY THE LICENSE ROOFER, AND AS WILL BE |
| | CONFIRMED BY THE INSPECTOR IN THE FIELD, THIS PERMIT |
| | CAN BE ISSUED AFTER THE FOLLOWING IS PROVIDED: |
| | |
| | ENGINEERING FOR ENHANCED FASTENING |
| | A PLAN SHOWING LOCATION OF THE REPAIR WHICH INCLUDES |
| | DISTANCE TO EDGES AS WELL AS ZONE 2 & ZONE 3 |
| | INFORMATION **OR** PROPOSE THAT ALL FASTENING TO BE IN |
| | ACCORDANCE WITH ZONE 3 REQUIREMENTS |
| | |
| | OPTION B: IF LICENSED ROOFER DETERMINES THAT OVER 25% |
| | OF THE ROOF AREA NEEDS REPAIR, A REROOF IS REQUIRED. |
| | REVISE APPLICATION TO REFLECT CORRECT SCOPE, PROVIDE |
| | ENHANCED FASTENING ENGINEERING |
| | |
| | OPTION C: IF OVER 25% OF THE ROOF AREA NEEDS REPAIR, |
| | BUT APPLICANT DOES NOT WISH TO DO A REROOF AS THE |
| | BUILDING IS TO BE DEMOLISHED, IT IS **POSSIBLE** THAT A |
| | TEMPORARY PATCH WILL BE CONSIDERED. IF THIS OPTION IS |
| | ELECTED, PLEASE CONTACT ME TO DISCUSS. |
| | |
| | |