2018-01-10 15:00:53BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PRODUCT APPROVALS SUBMITTED REQUIRE IMPACT RATED
 PROTECTIVE DEVICES.
 2. PROVIDE CITY OF WPB SCHEDULE FOR INSTALLATION OF
 OPENING PROTECTIVE DEVICES.
 3. PROVIDE PRODUCT APPROVALS FOR SHUTTERS.
  
 NOTE: MECHANICAL PERMIT 16061080 HAS EXPIRED WITH A
 FAILED INSPECTION STATUS. PLEASE ADDRESS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE SHUTTER SUBMITTALS.
  
  
  
  
2018-01-09 14:32:41DESCRIPTION STATES IMPACT RESISTANT, BUT SEE FL 14095.3
 REQUIRES IMPACT SYSTEM NOT PROVIDED FOR. PLEASE NOTIFY
 APPLICANT OF EXPIRED MECHANICAL PERMIT WITH FAILED
 INSPECTION 16061080.