Plan Review Notes
Plan Review Notes For Permit 17121069
Permit Number 17121069
Review Stop P
Sequence Number 2
Notes
Date Text
2018-05-02 08:40:352ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WATER TEMPERING DEVICE WATTS FL1170 IS NOT A
 CODE COMPLIANT FORR THE REQUIREMENTS OF TEMPERED WATER
 AT THE LAVATORY'S. PER MANUFACTURE SPECIFICATIONS
 A) IT IS A DISCONTINUED PRODUCT BECAUSE IT IS NOT LEAD
 FREE.
 B) IT DOES NOT MEET ASSE 1070 OR CSA B125.3 AS REQUIRED
 BY FBC PL 614.5
 PLEASE NOTE ON THE PLAN THAT THE WATER-TEMPERATURE
 LIMITING DEVICE IS REQUIRED FO THE LAVATORY'S AND MEETS
 ASSE 1070 OR CSA B125.3
  
 2. TWO COPY'S OF THE GREASE MONKEY SIZING CALCULATION
 SHALL BE SIGNED AND SEALED BY THE DESIGN PROFESSIONAL.
 PER WPB AMEND TO FBC 107.2.1.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  