Plan Review Notes
Plan Review Notes For Permit 17121069
Permit Number 17121069
Review Stop P
Sequence Number 1
Notes
Date Text
2018-01-22 12:57:341ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THIS SHALLL BE A CHANGE OF OCCUPANCY PER FBC EX 202
 AND 1001.2 PLEASE CHANGE PLAN TO INDICATE THIS. PER WPB
 AMEND TO FBC 107.2.1
  
 2. VALUATION OF JOB IS LOW PLEASE PROVIDE DOCUMENTATION
 TO SHOW VALUATION. PER WPB AMEND TO FBC 109.3 BUILDING
 PERMIT VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 3. SHT. 1.0A SHOWS CENTER OF TOILET OFF SIDE WALL AT
 18" MIN IT SHALL BE 16" MIN - 18" MAX. PER FBC ACC
 604.2
  
 4. THE GRAB BARS SHALL BE MEASURED FROM FROM FINISHED
 FLOOR TO TOP OF GRIPPING SURFACE PLEASE SHOW ON PLAN.
 PER FBC ACC 609.4
  
 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE PLAN SHOWS 19 MIN OFF FINISHED FLOOR IT
 SHALL BE 15 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB
 BARS. PER FBC ACC 604.7
  
 6. THE REQUIRED TEMPERED WATER AT THE LAVATORY'S SHAL
 BE DELIVERED BY TEMPERATURE LIMITING DEVISE COMPILING
 WITH ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 PROVIDE
 NOTE ON PLAN.
  
 7. TRAP PRIMERS ARE REQUIRED ON FLOOR DRAIN SHOW ON
 PLAN. PER FBC PL 1002.4
  
 8. PROVIDE GREASE INTERCEPTOR CALCULATION FROM SCHIER.
 PER WPB AMEND TO FBC 107.2.1
  
 9. A TESTPORT IS REQUIRED ON OUTLET OF GREASE
 INTERCEPTOR IT SHALL BE A 4" MIN TWOWAY CLEAN OUT OR A
 PRE MANUFACTURED TEST PORT. PER WPB UTIL. DEPT. PROVIDE
 DETAIL PER MANUFACTURE INSTALLATION GUIDE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  