| 2018-01-16 11:15:10 | 1ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING, | | | ENERGY CONSERVATION CODES | | | PERMIT #17121069 | | | 1/16/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE PROPOSED PROJECT IS CLASSIFIED AS A CHANGE OF | | | OCCUPANCY IN ACCORDANCE WITH SECTION 202 FBC-14 | | | EXISTING BUILDING CODE. WPB BUSINESS RECORDS SHOW | | | PREVIOUS TENANT WAS A DOG GROOMING BUSINESS- PLEASE | | | CORRECT THE LEVEL 3 REFERENCE ON THE COVER SHEET. REFER | | | TO SECTION C101.4.4 FBC-14 ENERGY CONSERVATION AND | | | SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT. SEE | | | | | | SECTION C401.2 FOR COMPLIANCE PATH INFORMATION. | | | | | | 2) A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR | | | SYSTEM OF THE 5-TON AC SYSTEM PER SECTION 606.2.1. | | | PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE | | | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS | | | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|