Plan Review Notes
Plan Review Notes For Permit 17121069
Permit Number 17121069
Review Stop M
Sequence Number 1
Notes
Date Text
2018-01-16 11:15:101ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #17121069
 1/16/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PROPOSED PROJECT IS CLASSIFIED AS A CHANGE OF
 OCCUPANCY IN ACCORDANCE WITH SECTION 202 FBC-14
 EXISTING BUILDING CODE. WPB BUSINESS RECORDS SHOW
 PREVIOUS TENANT WAS A DOG GROOMING BUSINESS- PLEASE
 CORRECT THE LEVEL 3 REFERENCE ON THE COVER SHEET. REFER
 TO SECTION C101.4.4 FBC-14 ENERGY CONSERVATION AND
 SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT. SEE
  
 SECTION C401.2 FOR COMPLIANCE PATH INFORMATION.
  
 2) A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF THE 5-TON AC SYSTEM PER SECTION 606.2.1.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  