Text |
| 2018-01-22 13:48:54 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE GAS LOAD CALCULATIONS SHOWS 2" @ 59' THE RISER | | | SHOWS A 11/2" PIPE PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 2. THE GAS LOAD CALCULATIONS SHOWS 59' OF DEVELOPED | | | LENGTH THE CUT SECTION ON THE RISER ADD UP TO 31' | | | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. THE RISER SHOWS A GRIDDLE @ 105K AND A GRIDDLE @ 60K | | | IS THERE 2 GRIDDLES PLEASE CLARIFY. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 4. ON THE RISER THE MANIFOLD PIPING BEHIND EQUIPMENT IS | | | SHOWN AS 1" @ 788K IT SHALL BE 11/2" @ 518K PER FBC FG | | | TABLE 402.4(2) PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|