Plan Review Notes
Plan Review Notes For Permit 17121049
Permit Number 17121049
Review Stop M
Sequence Number 2
Notes
Date Text
2018-04-20 10:37:552ND REVIEW FBC-2017 MECHANICAL
 PERMIT #17121049
 4/20/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M102: PLEASE SHOW THE LOCATIONS OF THE GUARD RAILS
 ON THE ROOF AND PROVIDE STRUCTURAL DETAILS FOR
 INSTALLATION AND ATTACHMENT TO THE EXISTING STRUCTURE-
 SECTION 304.11.
  
 2) M201: THE O/A CALCULATIONS FOR THE DINING ROOM AS
 SHOWN IN THE SCHEDULE ARE NOT IN COMPLIANCE WITH TABLE
 403.3. IN ACCORDANCE WITH THE TABLE- 154 OCCUPANTS X
 7.5 CFMS EACH= 1155 CFMS + 394= 1549 CFMS OF O/A
 REQUIRED. THE SCHEDULE INDICATES A DEFICIENT AMOUNT OF
 700 CFMS TO BE PROVIDED FOR THE DINING ROOM.
  
 3) M201: THE COMBUSTION AIR CALCULATIONS DO NOT INCLUDE
 THE WOOD-FIRED CHARBROILER- SEE SECTION 701.1 AND
 PROVIDE THE CALCULATIONS AS RECOMMENDED BY THE
 MANUFACTURER. PLEASE NOTE THAT THE SUBMITTED PRODUCT
 CUT SHEETS DO NOT INDICATE THE APPLIANCE IS UL 2162
 LISTED AND LABELED, AND THEREFORE IS NOT APPROVED FOR
 INSTALLATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719