| 2018-04-20 10:37:55 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #17121049 |
| | 4/20/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) M102: PLEASE SHOW THE LOCATIONS OF THE GUARD RAILS |
| | ON THE ROOF AND PROVIDE STRUCTURAL DETAILS FOR |
| | INSTALLATION AND ATTACHMENT TO THE EXISTING STRUCTURE- |
| | SECTION 304.11. |
| | |
| | 2) M201: THE O/A CALCULATIONS FOR THE DINING ROOM AS |
| | SHOWN IN THE SCHEDULE ARE NOT IN COMPLIANCE WITH TABLE |
| | 403.3. IN ACCORDANCE WITH THE TABLE- 154 OCCUPANTS X |
| | 7.5 CFMS EACH= 1155 CFMS + 394= 1549 CFMS OF O/A |
| | REQUIRED. THE SCHEDULE INDICATES A DEFICIENT AMOUNT OF |
| | 700 CFMS TO BE PROVIDED FOR THE DINING ROOM. |
| | |
| | 3) M201: THE COMBUSTION AIR CALCULATIONS DO NOT INCLUDE |
| | THE WOOD-FIRED CHARBROILER- SEE SECTION 701.1 AND |
| | PROVIDE THE CALCULATIONS AS RECOMMENDED BY THE |
| | MANUFACTURER. PLEASE NOTE THAT THE SUBMITTED PRODUCT |
| | CUT SHEETS DO NOT INDICATE THE APPLIANCE IS UL 2162 |
| | LISTED AND LABELED, AND THEREFORE IS NOT APPROVED FOR |
| | INSTALLATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |