Plan Review Notes
Plan Review Notes For Permit 17121049
Permit Number 17121049
Review Stop E
Sequence Number 2
Notes
Date Text
2018-05-24 10:42:32 
  
  
2018-04-25 14:25:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 ALL PREVIOUS ITEMS HAVE BEEN ADDRESSED SATISFACTORILY.
 SEE NEW COMMENT BELOW.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5.CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
  
 NEW COMMENT:
  
 11. THE LOAD CALCULATION PROVIDED SHOWS THAT THERE IS A
 DEMAND LOAD OF 391 AMPS FOR SERVICE. THE WIRE SPECIFIED
 IN DESIGN, 500 KCMIL COPPER, IS RATED FOR 380 AMPS.
 PROVIDE CORRECTION. NEC 310.15(B)(16)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  