| 2018-04-23 11:45:25 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | W.P.B. PERMIT: 17121049 |
| | ADD: 1603 DIXIE HWY. |
| | CONT: MARION CONSTRUCTION INC. |
| | TEL: 561-324-3163 |
| | E-MAIL: [email protected] |
| | |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING (PREVIOUS REVIEW WAS BY JAMES |
| | A.WITMER) |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17121049 |
| | ADD: 1603 S. DIXIE HWY. |
| | CONT: MARION CONSTRUCTION INC. |
| | TEL: 561-324-3163 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. JAN. 25/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2A) COMPLIED. |
| | |
| | 2B) COMPLIED. |
| | |
| | 2C) COMPLIED. |
| | |
| | 2D) COMPLIED. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) (THIS COMMENT WAS NOT ADDRESSED. PLANS DO NOT DETAIL |
| | HOW THIS ISSUE WILL BE ADDRESSED.) SHEET C1 SHOWS A |
| | 1250 GALLON GREASE TRAP WITHIN 1-0 FOOT OF THE PROPOSED |
| | COURTYARD CANOPY. SCHEDULING AND BUILDING SEQUENCE WILL |
| | BE ESSENTIAL TO MAINTAINING SOLID GROUND BENEATH THE |
| | PROPOSED FOUNDATION. PLEASE SEE THE REQUIREMENTS FOR |
| | SETBACKS FOR POOLS FROM FOUNDATIONS. PLEASE PROVIDE ON |
| | THE PLANS SEQUENCE OF SCHEDULING FOR COMPLIANCE. |
| | FBC-B 1804.1 EXCAVATION NEAR FOUNDATIONS. EXCAVATION |
| | FOR ANY PURPOSE SHALL NOT REMOVE LATERAL SUPPORT FROM |
| | ANY FOUNDATION WITHOUT FIRST UNDERPINNING OR PROTECTING |
| | THE FOUNDATION AGAINST SETTLEMENT OR LATERAL |
| | TRANSLATION. |
| | FBC-B 1808.7.3 POOLS. THE SETBACK BETWEEN POOLS |
| | REGULATED BY THIS CODE AND SLOPES SHALL BE EQUAL TO |
| | ONE-HALF THE BUILDING FOOTING SETBACK DISTANCE REQUIRED |
| | BY THIS SECTION. THAT PORTION OF THE POOL WALL WITHIN A |
| | HORIZONTAL DISTANCE OF 7 FEET (2134 MM) FROM THE TOP OF |
| | THE SLOPE SHALL BE CAPABLE OF SUPPORTING THE WATER IN |
| | THE POOL WITHOUT SOIL SUPPORT. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) (THIS ITEM WILL BE NOTED ON THE PLANS AS A PROVISO |
| | ITEM.) SHEET S100 CUT SECTIONS AND S200 SHOW NEW STEEL |
| | COLUMNS, STEEL BEAMS, BAR JOIST, AND METAL B DECK. |
| | WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION. |
| | 2014 FBC-B 2204.1 WELDING |
| | 2014 FBC-B 2204.2 BOLTING. |
| | |
| | 7) (THE ROOFING AND MECHANICAL A/C PRODUCT APPROVALS |
| | WILL BE DEFERRED UNTIL SUBMISSION FOR SUB-PERMITS PER |
| | YOUR REQUEST.) PLEASE PROVIDE COMPLIANCE WITH 2014 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF TOP |
| | VENTILATORS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 8) (THIS COMMENT WAS NOT ADDRESSED. THE SPECIFIC |
| | INFORMATION WAS NOT MARKED UP IN THE PRODUCT |
| | APPROVALS.) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY |
| | ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER |
| | OF RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER'S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 9A) (THIS COMMENT WAS NOT ADDRESSED. DESIGNER OF |
| | RECORD'S SHOP DRAWING REVIEW STAMP IS NOT ON THE |
| | PRODUCT APPROVALS.) W. P. B. 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | |
| | 9B) ( THE ROOFING, A/C STANDS AND ALUMINUM TRELLIS WILL |
| | BE NOTED AS DEFERRED SUBMITALS ON THE PLANS.) 107.3.4.2 |
| | DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| | DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF |
| | THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 10) ( THIS INFORMATION IS REQUIRED TO BE SUBMITTED WITH |
| | THE DEFERRED ROOFING SUBMITTALS. ) ROOFING/ FLAT ROOFS: |
| | FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | |
| | 11A) COMPLIED. |
| | |
| | |
| | 11B) (THIS INFORMATION IS REQUIRED TO BE SUBMITTED WITH |
| | THE DEFERRED SUBMITTALS. ) FOR ROOF TOP A/C STAND |
| | PRODUCT APPROVAL A MIAMI-DADE OR FLORIDA PRODUCT |
| | APPROVAL IS TO BE SUBMITTED, REVIEWED BY THE DESIGNER |
| | OF RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS |
| | CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP |
| | COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF |
| | HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED |
| | THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT |
| | VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND |
| | TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY |
| | THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO |
| | THE BUILDING DEPARTMENT. |
| | |
| | 12) COMPLIED. |
| | |
| | 13) (THIS COMMENT WAS NOT ADDRESSED. SEE 13B AND 14B.) |
| | SHEET A401 IS A FLOOR PLAN WITH SEATING BUT DOES NOT |
| | SHOW COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE; |
| | |
| | 13A) (THIS COMMENT WAS NOT ADDRESSED. SEE 13B. ) 226.1 |
| | WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION |
| | OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING |
| | SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL |
| | COMPLY WITH 902. |
| | |
| | 13B) (THIS COMMENT WAS NOT ADDRESSED. SHOW ACCESSIBLE |
| | SEATING AND FLOOR SPACE AT THE COFFEE BAR.) 226.2 |
| | DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED |
| | TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE |
| | SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK |
| | SURFACES. |
| | |
| | 13C) (THIS COMMENT WAS NOT ADDRESSED. SEE 13B AND 14B. |
| | ) THE 902.1 DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK |
| | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| | COUNTERS, AND WHERE COVERED BY THE ABA SCOPING |
| | PROVISIONS, EMPLOYEE WORK STATIONS. |
| | |
| | 14)(A) (THIS COMMENT WAS NOT ADDRESSED. SEE 13B. ) |
| | 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | SHALL BE PROVIDED. KNEE AND TOE CLEARANCE COMPLYING |
| | WITH 306 SHALL BE PROVIDED. |
| | |
| | 14)(B)(THIS COMMENT WAS NOT ADDRESSED. SEE 13B AND |
| | 14B.) PROVIDE AN ELEVATION OF THE COFFEE BAR AND |
| | SERVICE COUNTER THAT SHOWS COMPLIANCE.) 902.3 HEIGHT. |
| | THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE |
| | 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | |
| | 15) (THIS COMMENT WAS NOT ADDRESSED. BRAILLE SHALL BE |
| | POSITIONED BELOW THE CORRESPONDING TEXT AND WITHIN THE |
| | 48" REACH RANGE.) SIGNAGE 703. 703.1 SIGNS SHALL COMPLY |
| | WITH 703. WHERE BOTH VISUAL AND TACTILE CHARACTERS ARE |
| | REQUIRED, EITHER ONE SIGN WITH BOTH VISUAL AND TACTILE |
| | CHARACTERS, OR TWO SEPARATE SIGNS, ONE WITH VISUAL, AND |
| | ONE WITH TACTILE CHARACTERS, SHALL BE PROVIDED. |
| | |
| | 15A) (THIS COMMENT WAS NOT ADDRESSED. BRAILLE SHALL BE |
| | POSITIONED BELOW THE CORRESPONDING TEXT AND WITHIN THE |
| | 48" REACH RANGE.) 2014 ACCESSIBILITY CODE. 703.4.1 |
| | HEIGHT ABOVE FINISH FLOOR OR GROUND. TACTILE CHARACTERS |
| | ON SIGNS SHALL BE LOCATED 48 INCHES MINIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE |
| | BASELINE OF THE LOWEST TACTILE CHARACTER AND 60 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE, |
| | MEASURED FROM THE BASELINE OF THE HIGHEST TACTILE |
| | CHARACTER. |
| | |
| | 15B) (THIS COMMENT WAS NOT ADDRESSED. BRAILLE SHALL BE |
| | POSITIONED BELOW THE CORRESPONDING TEXT AND WITHIN THE |
| | 48" REACH RANGE.) SIGNAGE. 703.4.1 HEIGHT ABOVE FINISH |
| | FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE |
| | LOCATED 48 INCHES MINIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND SURFACE, MEASURED FROM THE BASELINE OF THE |
| | LOWEST TACTILE CHARACTER AND 60 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE |
| | BASELINE OF THE HIGHEST TACTILE CHARACTER. |
| | |
| | 16) CLOSING. WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 17) (NEW COMMENT.) THIS WORK AREA FOR THIS PROJECT |
| | EXCEEDS 50 PERCENT OF THE AGGREGATE AREA OF THE |
| | BUILDING, THEREFORE BASED ON FBC EXISTING BUILDING |
| | SECTION 505 THIS IS A LEVEL 3 ALTERATION. PLEASE REVISE |
| | THE CODE RESEARCH SCHEDULE ON SHEET A000 FROM LEVEL 2 |
| | TO LEVEL 3 ALTERATION. |
| | |
| | 18) (NEW COMMENT.) THE WRONG ADDITION OF NFPA 101 LIFE |
| | SAFETY CODE IS SPECIFIED ON SHEET A000. THE 2014 FBC |
| | REFERENCES THE 2012 EDITION OF NFPA 101 IN CHAPTER 35. |
| | PLEASE REVISE. |
| | |
| | 19) (NEW COMMENT.)ON SHEET A 403 NOTE ONE UNDER LIFE |
| | SAFETY SIGNAGE STATES THAT THE ADA SIGNS SHALL BE |
| | PLACED AT EACH OF THE FOUR BATHROOMS. THE PLANS ONLY |
| | SHOW TWO BATHROOMS. PLEASE CORRECT. FBC 107.2.1 |
| | |
| | 20) (NEW COMMENT.) THE HEIGHT OF THE GRAB BARS IS |
| | MEASURED TO THE TOP OF THE GRIPPING SURFACE PER 2014 |
| | FBC ACCESSIBILITY 609.4. PLEASE REVISE DRAWINGS ON |
| | SHEET A402 THAT SHOW THE MEASUREMENT TO THE CENTER LINE |
| | OF THE GRAB BAR. |
| | |
| | 21) (NEW COMMENT.) THE ELEVATIONS ON SHEETS A301 AND |
| | A302 SHOWS GYPSUM BOARD CEILING PANELS AND FURRING |
| | BELOW THE STEEL BAR JOISTS. PROVIDE ADDITIONAL DETAILS |
| | INCLUDING DEAD LOADS TO SHOW HOW THIS CEILING SYSTEM |
| | WILL BE SUSPENDED FROM THE BAR JOISTS. FBC 107.2.1.3 |
| | |
| | 22) END OF COMMENTS. SEE COMMENT NUMBER 16 FROM FIRST |
| | REVIEW. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |