2018-02-02 11:59:251ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE OCCUPANT LOAD INCLUDING OUTDOOR PAVILION AND
 OUTDOOR SEATING. PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE PLUMBING FIXTURE COUNT BREAKDOWN. PER WPB
 AMEND TO FBC 107.2.1 AND FBC PL 403.1.1
  
 3. PROVIDE DETAIL FOR EMERGENCY SCUPPER TO SHOW
 COMPLIANCE WITH FBC 1503.4.2.1
  
 4. PROVIDE STORM DRAIN ISOMETRIC SHOWING SQFT AND SLOPE
 OF PIPE. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 5. THE DIMENSION OF THE ACCESSIBLE BATHEOOMS ARE TO
 SMALL TO COMPLY WITH FBC ACC 604, 606.2 IT SHOULD BE A
 MIN OF 7' 1" TO ACCOMMODATE THE CLEAR FLOOR SPACE.
 PLEASE SHOW THE CLEAR FLOOR SPACE WITH THE DIMENSIONS
 TO COMPLY WITH FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 604.3.2 OVERLAP.
 THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6. PLEASE SHOW COMPLIANCE WITH FBC ACC
  
 A) 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
  
 B)609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 C) 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 D) 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 E) 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 7. HOT WATER PIPING IN AUTOMATIC TEMPERATURE
 MAINTENANCE SYSTEMS SHALL BE INSULATED WITH 1 INCH (25
 MM) OF INSULATION. PER FBC PL [E] 607.5
  
 8. SHT. C-1 SHOWS A PROPOSED 1250 GAL GREASE
 INTERCEPTOR SHT. P101 NOTE ON GREASE PIPING REFERS TO
 AN EXISTING GREASE TRAP PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 9. PLEASE PROVIDE DETAIL OF INTERIOR OF GREASE
 INTERCEPTOR AND A DETAIL OF THE INLET AND OUTLET
 PIPING. PER WPB AMEND TO FBC 107.2.1
  
 10. SHT. P103 PLEASE LABEL EMERGENCY SCUPPERS. PER WPB
 AMEND TO FBC 107.2.1
  
 11. SHT. P201 THE BRANCH DRAIN FOR THE THE DROP IN SINK
 P66 SHALL CONNECT TO THE BUILDING DRAIN SEPARATELY FROM
 THR BATHROOM GROUP IT SHALL NOT CONNECT THRU THE
 BATHROOM GROUP WET VENT. PER FBC PL 912.1
  
 12. PLEASE SEPARATE THE GREASE ISOMETRIC AND SANITARY
 ISOMETRIC. PER WPB AMEND TO FBC 107.2.1
  
 13. SHT. 201 UNDER THE PLUMBING SPECIFICATIONS #2(A)
 THE CODE REQUIREMENT FOR THIS PROJECT SHALL BE THE
 FLORIDA BUILDING CODE 2014 5TH EDITION, FLORIDA
 BUILDING CODE PLUMBING, FLORIDA BUILDING CODE
 ACCESSIBILITY. FLORIDA BUILDING CODE FUEL GAS
 THE SBCCI IS A OUT OF DATE CODE.
  
 14. ALL FIXTURES IN KITCHEN AREA SHALL DISCHARGE TO THE
 GREASE INCEPTOR. PER FBC PL 1003.3.1
  
 15. DRAIN FOR THE-ICE MACHINES AND SINKS IN COFFEE BAR
 AND SERVICE COUNTER SHALL NOT DISCHARGE TO THE GREASE
 INTERCEPTOR. PER FBC PL 1003.3.1
  
 16. PLEASE PLACE NOTE ON THE PLAN A SEPARATE PERMIT IS
 REQUIRED FOR NEW GREASE INTERCEPTORS AND BACKFLOW ON
 THE WATER SERVICE. PER WPB AMEND TO FBC 107.2.1
  
 17. SHUT OFF VALVES ARE REQUIRED ON ALL DROPS PLEASE
 SHOW ON WATER ISOMETRIC. PER FBC PL 606.1(5)
  
 18. SHOW AIR HAMMER ARRESTORS ON WATER ISOMETRIC. PER
 FBC PL 604.9
  
 19 BACKFLOWS ARE REQUIRED ON ICE MACHINES, WATER
 FILTERS, BEVERAGE MACHINES AND COFFEE MAKERS. PER FBC
 PL 608.3, 608.16.1 AND 608.16.10
  
 20. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711