2018-01-29 12:14:271ST REVIEW FBC-2014 MECHANICAL, FUEL GAS, EXISTING
 BUILDING CODES
 PERMIT #17121049
 1/29/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE ARE TWO M201 PLAN SHEETS IN EACH PLAN SET.
 PLEASE CHANGE ONE OF THE SHEETS TO M202.
  
 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION 312.1 FBC-14 MECHANICAL.
  
 3) SHEET M102: PLEASE PROVIDE NOTES ON THE PLAN TO
 VERIFY COMPLIANCE WITH THE FOLLOWING REQUIREMENTS FOR
 THE NEW RTU'S: A) A MINIMUM 42" HIGH GUARD OR PARAPET
 WILL BE INSTALLED ALONG THE ROOF EDGES ADJACENT TO THE
 NEW RTU'S. B) A MINIMUM 30X30 IN. WORKING SPACE WILL BE
 PROVIDED ON THE SERVICE SIDES OF THE RTU'S. C) A
 PERMANENT LADDER, EITHER INTERIOR OR EXTERIOR OF THE
  
 BUILDING, SHALL BE INSTALLED IF ACESSING THE RTU'S
 REQUIRES PERSONEL TO CLIMB HIGHER THAN 16 FEET ABOVE
 GRADE.
  
 4) M101: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 RETURN AIR SYSTEMS OF EACH NEW RTU. SHOW THE LOCATION
 OF THE DEVICES ON THE PLAN AND PROVIDE A SEQUENCE OF
 OPERATION FOR FAN SHUTDOWN IF ONE DAMPER OR ANOTHER
 ACTUATES- SECTION 606.2.1- 606.4.1.
  
 5) M201: THE FRESH AIR CALCULATIONS ARE NOT IN
 COMPLIANCE WITH TABLE 403.3. PLEASE INDICATE THE SQUARE
 FOOTAGES OF ALL OCCUPIED ROOMS AND SPACES, AND PROVIDE
 CALCULATIONS USING THE PEOPLE OUTDOOR AIRFLOW RATE (CFM
 PER PERSON) ADDED TO THE AREA OUTDOOR AIRFLOW RATE.
  
 6) M201: THE AIR BALANCE SCHEDULE DOES NOT PROVIDE
 EXHAUST AND MAKEUP CFMS FOR THE KITCHEN HOODS
  
 7) PROVIDE A KITCHEN EQUIPMENT LAYOUT PLAN AND SCHEDULE
 THAT INCLUDES THE MAKES AND MODELS AND BTU CAPACITIES
 FOR ALL GAS-FIRE COOKING APPLIANCES.
  
 8) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING
 APPLIANCES AND SHOW HOW THE AIR IS BEING PROVIDED-
 SECTION 304 FBC-14 FUEL GAS.
  
 9) M201 & S302: THE RTU AND CURB ATTACHMENT DETAIL ON
 THE MECHANICAL PLAN DOES NOT MATCH THE DETAIL ON THE
 STRUCTURAL PLAN- PLEASE CORRECT.
  
 10) M201: INDICATE HOW THE DUCT SUPPORT LEG PLATES ARE
 ATTACHED TO THE STRUCTURE.
  
 11) M201: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF ALL ROOFTOP EQUIPMENT AND SUPPORTS-
 SECTION 1609 FBC-14 BUILDING.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER