| 2018-01-29 12:14:27 | 1ST REVIEW FBC-2014 MECHANICAL, FUEL GAS, EXISTING |
| | BUILDING CODES |
| | PERMIT #17121049 |
| | 1/29/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THERE ARE TWO M201 PLAN SHEETS IN EACH PLAN SET. |
| | PLEASE CHANGE ONE OF THE SHEETS TO M202. |
| | |
| | 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEMS- SECTION 312.1 FBC-14 MECHANICAL. |
| | |
| | 3) SHEET M102: PLEASE PROVIDE NOTES ON THE PLAN TO |
| | VERIFY COMPLIANCE WITH THE FOLLOWING REQUIREMENTS FOR |
| | THE NEW RTU'S: A) A MINIMUM 42" HIGH GUARD OR PARAPET |
| | WILL BE INSTALLED ALONG THE ROOF EDGES ADJACENT TO THE |
| | NEW RTU'S. B) A MINIMUM 30X30 IN. WORKING SPACE WILL BE |
| | PROVIDED ON THE SERVICE SIDES OF THE RTU'S. C) A |
| | PERMANENT LADDER, EITHER INTERIOR OR EXTERIOR OF THE |
| | |
| | BUILDING, SHALL BE INSTALLED IF ACESSING THE RTU'S |
| | REQUIRES PERSONEL TO CLIMB HIGHER THAN 16 FEET ABOVE |
| | GRADE. |
| | |
| | 4) M101: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| | RETURN AIR SYSTEMS OF EACH NEW RTU. SHOW THE LOCATION |
| | OF THE DEVICES ON THE PLAN AND PROVIDE A SEQUENCE OF |
| | OPERATION FOR FAN SHUTDOWN IF ONE DAMPER OR ANOTHER |
| | ACTUATES- SECTION 606.2.1- 606.4.1. |
| | |
| | 5) M201: THE FRESH AIR CALCULATIONS ARE NOT IN |
| | COMPLIANCE WITH TABLE 403.3. PLEASE INDICATE THE SQUARE |
| | FOOTAGES OF ALL OCCUPIED ROOMS AND SPACES, AND PROVIDE |
| | CALCULATIONS USING THE PEOPLE OUTDOOR AIRFLOW RATE (CFM |
| | PER PERSON) ADDED TO THE AREA OUTDOOR AIRFLOW RATE. |
| | |
| | 6) M201: THE AIR BALANCE SCHEDULE DOES NOT PROVIDE |
| | EXHAUST AND MAKEUP CFMS FOR THE KITCHEN HOODS |
| | |
| | 7) PROVIDE A KITCHEN EQUIPMENT LAYOUT PLAN AND SCHEDULE |
| | THAT INCLUDES THE MAKES AND MODELS AND BTU CAPACITIES |
| | FOR ALL GAS-FIRE COOKING APPLIANCES. |
| | |
| | 8) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING |
| | APPLIANCES AND SHOW HOW THE AIR IS BEING PROVIDED- |
| | SECTION 304 FBC-14 FUEL GAS. |
| | |
| | 9) M201 & S302: THE RTU AND CURB ATTACHMENT DETAIL ON |
| | THE MECHANICAL PLAN DOES NOT MATCH THE DETAIL ON THE |
| | STRUCTURAL PLAN- PLEASE CORRECT. |
| | |
| | 10) M201: INDICATE HOW THE DUCT SUPPORT LEG PLATES ARE |
| | ATTACHED TO THE STRUCTURE. |
| | |
| | 11) M201: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR |
| | INSTALLATION OF ALL ROOFTOP EQUIPMENT AND SUPPORTS- |
| | SECTION 1609 FBC-14 BUILDING. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |