2018-02-02 14:23:321ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND
 INSTILLATION GUIDE FOR ALL GAS EQUIPMENT AND REGULATORS
 TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58,
 AND FBC-2014 FUEL GAS SEC. 402.2
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR KITCHEN
 EQUIPMENT PER THE FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. SHT P202 THE REFERENCED SIZING TABLE 402.4(4) IS FOR
 LESS THAN 2PSI WITH A PRESSURE DROP OF 6.0" WC THE
 TABLE FOR 2PSI SCH 40 STEEL PIPE IS 402.4(5) PLEASE
 CLARIFY PER FBC FG 402.4
  
 4. SHOW REGULATORS SHUT OFF VALVES AND SEDIMENT TRAPS
 ON RISER. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  