| Plan Review Notes For Permit 17121049 |
| Permit Number |
17121049 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-02-02 14:23:32 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND | | | INSTILLATION GUIDE FOR ALL GAS EQUIPMENT AND REGULATORS | | | TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, | | | AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR KITCHEN | | | EQUIPMENT PER THE FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 3. SHT P202 THE REFERENCED SIZING TABLE 402.4(4) IS FOR | | | LESS THAN 2PSI WITH A PRESSURE DROP OF 6.0" WC THE | | | TABLE FOR 2PSI SCH 40 STEEL PIPE IS 402.4(5) PLEASE | | | CLARIFY PER FBC FG 402.4 | | | | | | 4. SHOW REGULATORS SHUT OFF VALVES AND SEDIMENT TRAPS | | | ON RISER. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|