Plan Review Notes
Plan Review Notes For Permit 17121049
Permit Number 17121049
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-01-03 17:00:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO INDICATIONS OF THE EXISTING OCCUPANCY
 CLASSIFICATION AND THE PROPOSED OCCUPANCY
 CLASSIFICATION.
  
 PER NFPA 101, CHAPTER 6
  
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR
 STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2
 THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A QUESTION OF PROPER
 CLASSIFICATION IN ANY INDIVIDUAL CASE.
  
 PLEASE PROVIDE APPLICABLE DETAILS.
  
  
  
 2) THERE IS NO INDICATIONS OF OCCUPANCY LOAD
 CALCULATIONS OF THE PROPOSED PROJECT.
  
 PER NFPA 101, CHAPTER 7
  
 7.3.1 OCCUPANT LOAD.
 7.3.1.1 SUFFICIENT CAPACITY.
 7.3.1.1.1 THE TOTAL CAPACITY OF THE MEANS OF EGRESS FOR
 ANY STORY, BALCONY, TIER, OR OTHER OCCUPIED SPACE SHALL
 BE SUFFICIENT FOR THE OCCUPANT LOAD THEREOF.
 7.3.1.1.2 FOR OTHER THAN EXISTING MEANS OF EGRESS,
 WHERE MORE THAN ONE MEANS OF EGRESS IS REQUIRED, THE
 MEANS OF EGRESS SHALL BE OF SUCH WIDTH AND CAPACITY
 THAT THE LOSS OF ANY ONE MEANS OF EGRESS LEAVES
 AVAILABLE NOT LESS THAN 50 PERCENT OF THE REQUIRED
 CAPACITY.
 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY
 BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE
 NUMBER OF PERSONS DETERMINED BY DIVIDING THE FLOOR AREA
 ASSIGNED TO THAT USE BY THE OCCUPANT LOAD FACTOR FOR
 THAT USE AS SPECIFIED IN TABLE 7.3.1.2, FIGURE
 7.3.1.2(A), AND FIGURE 7.3.1.2(B). WHERE BOTH GROSS AND
 NET AREA FIGURES ARE GIVEN FOR THE SAME OCCUPANCY,
 CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA
 FIGURE TO THE GROSS AREA OF THE PORTION OF THE BUILDING
 DEVOTED TO THE USE FOR WHICH THE GROSS AREA FIGURE IS
 SPECIFIED AND BY APPLYING THE NET AREA FIGURE TO THE
 NET AREA OF THE PORTION OF THE BUILDING DEVOTED TO THE
 USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED.
  
 PLEASE PROVIDE APPCIABLE DETAILS.
  
  
  
  
 3) SHEETS A 101 & 401 - THERE ARE NOTE INDICATIONS OF A
 "FOOD SERVICE EQUIPMENT DRAWINGS" FOR THE KITCHEN AREA;
 HOWEVER, NO DRAWING SHEETS WERE FOUND OR ANY EQUIPMENT
 IDENTIFIED.
  
 PER NFPA 101 CHAPTER 9 & NFPA 96, CHAPTER 4
  
 CHAPTER 9 BUILDING SERVICE AND FIRE PROTECTION
 EQUIPMENT
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 96, CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE REQUIREMENTS OF THIS STANDARD.
 10.1.2* COOKING EQUIPMENT THAT PRODUCES GREASE-LADEN
 VAPORS AND THAT MIGHT BE A SOURCE OF IGNITION OF GREASE
 IN THE HOOD, GREASE REMOVAL DEVICE, OR DUCT SHALL BE
 PROTECTED BY FIRE-EXTINGUISHING EQUIPMENT.
  
 PLEASE PROVIDE SPECIFIC DETAILS OF ALL EQUIPMENT.
  
  
  
  
 4) SHEET A 200 - A LIGHWEIGHT ROOF TRUSS SIGN IS
 REQUIRED AT THE FRONT DOOR AREA PER FLORIDA STATUTE.
 LIGHTWEIGHT ROOF TRUSS DESIGN IS INDICATED ON OTHER
 SHEETS.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
  
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND
 COMPLIANCE.
  
  
  
  
 5) SHEET M 101 - THERE IS KITCHEN EQUIPMENT INDICATED
 IN THE KITCHEN AREA.
  
 PER # 3 ABOVE THE HOOD VENT AND FIRE SUPPRESSION
 SYSTEMS IN THE KITCHEN AREA SHALL BE UNDER SEPARATE
 SHOP DRAWINGS EACH.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND
 COMPLIANCE.
  
  
  
 6) E 102 -THERE IS NO EXIT SIGN INDICATED OVER THE REAR
 DOOR AREA NOR THE REAR DOOR FROM THE REAR COVERED
 PARTIO. A SECOND EXIT IS REQUIRED AND IT IS REQUIRED TO
 BE MARKED.
  
  
 7.7.3 ARRANGEMENT AND MARKING OF EXIT DISCHARGE.
 7.7.3.1 WHERE MORE THAN ONE EXIT DISCHARGE IS REQUIRED,
 EXIT DISCHARGES SHALL BE ARRANGED TO MEET THE
 REMOTENESS CRITERIA OF 7.5.1.3.
 7.7.3.2 THE EXIT DISCHARGE SHALL BE ARRANGED AND MARKED
 TO MAKE CLEAR THE DIRECTION OF EGRESS TRAVEL FROM THE
 EXIT DISCHARGE TO A PUBLIC WAY.
  
 7.7.4 COMPONENTS OF EXIT DISCHARGE. DOORS, STAIRS,
 RAMPS, CORRIDORS, EXIT PASSAGEWAYS, BRIDGES, BALCONIES,
 ESCALATORS, MOVING WALKS, AND OTHER COMPONENTS OF AN
 EXIT DISCHARGE SHALL COMPLY WITH THE DETAILED
 REQUIREMENTS OF THIS CHAPTER FOR SUCH COMPONENTS.
  
  
 PLEASE PROVIDE EXIT SIGNS AT THESE AREAS.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL