| 2018-02-05 15:35:27 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| | 107.2.1 |
| | 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 |
| | 3. PROVIDE LETTER FROM POWER COMPANY TO CONFIRM STATED |
| | AIC VALUE AT SERVICE. NEC 110.9, 110.10 |
| | 4. SHEET E102, NOTE 5, STATES THAT THE EMERGENCY AND |
| | EXIT LIGHTS SHOULD BE CONNECTED TO THE CIRCUIT B-3. |
| | EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED FROM |
| | THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE |
| | CORRECTION. NEC 700.12(F) |
| | 5. PLAN SHOWS THE DIMMING CONTROLS REQUIRED, BUT DOES |
| | NOT APPEAR TO SHOW THE CIRCUITS AS CONTROLLED THROUGH |
| | EITHER A TIMER OR OCCUPANCY SENSOR AS REQUIRED PER |
| | ENERGY CODE. PROVIDE CLARIFICATION. FBC EC 405.2.2, |
| | 405.2.2.2 |
| | 6. ALL RECEPTACLES IN KITCHEN AND PREP AREAS REQUIRE |
| | GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8 |
| | 7. ALL RECEPTACLES WITHIN 6 FEET OF A SINK REQUIRE GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8 |
| | 8. PROVIDE SHOW WINDOW OUTLETS REQUIRED PER CODE. NEC |
| | 210.62 |
| | 9. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 10. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |