2018-02-05 15:35:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 3. PROVIDE LETTER FROM POWER COMPANY TO CONFIRM STATED
 AIC VALUE AT SERVICE. NEC 110.9, 110.10
 4. SHEET E102, NOTE 5, STATES THAT THE EMERGENCY AND
 EXIT LIGHTS SHOULD BE CONNECTED TO THE CIRCUIT B-3.
 EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED FROM
 THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 5. PLAN SHOWS THE DIMMING CONTROLS REQUIRED, BUT DOES
 NOT APPEAR TO SHOW THE CIRCUITS AS CONTROLLED THROUGH
 EITHER A TIMER OR OCCUPANCY SENSOR AS REQUIRED PER
 ENERGY CODE. PROVIDE CLARIFICATION. FBC EC 405.2.2,
 405.2.2.2
 6. ALL RECEPTACLES IN KITCHEN AND PREP AREAS REQUIRE
 GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 7. ALL RECEPTACLES WITHIN 6 FEET OF A SINK REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
 8. PROVIDE SHOW WINDOW OUTLETS REQUIRED PER CODE. NEC
 210.62
 9. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 10. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER