| Date |
Text |
| 2018-01-29 15:11:29 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. RENOVATION OF AN ACCESSORY BUILDING TO A HABITABLE |
| | DWELLING UNIT IS A CHANGE OF OCCUPANCY/CHANGE OF USE |
| | PER THE FBC EXISTING BLDG. SECTION 407. |
| | 2. ALL STRUCTURAL ELEMENTS SHALL BE EVALUATED BY A |
| | LICENSED FLORIDA PROFESSIONAL ENGINEER. |
| | 3. ENGINEER TO SUBMIT EVALUATION REPORT AS PART OF |
| | RE-SUBMITTAL. |
| | 4. PROVIDE SITE PLAN. |
| | 5. PROVIDE COPY OF CURRENT SURVEY. |
| | 6. PROVIDE ENERGY SUBMITTAL. |
| | 7. PROVIDE PRODUCT APPROVALS FOR EXTERIOR CLADDING, |
| | ROOFING, DOORS AND WINDOWS. |
| | 8. IF WINDOWS AND DOORS ARE NOT IMPACT RATED, PROVIDE |
| | SCHEDULE FOR INSTALLATION OF OPENING PROTECTION |
| | DEVICES. |
| | |
| | FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| | AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION |
| | PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL |
| | FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING |
| | DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: |
| | |
| | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| | |
| | _ OR _ |
| | |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE EXTERIOR CLADDING, ROOFING, |
| | WINDOW AND DOOR SUBMITTALS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| 2018-01-09 16:59:01 | SCOPE OF WORK ON PLAN MAY NOT STATE "CONVERT STORAGE |
| | BUILDING TO GUEST HOUSE.' |