| Plan Review Notes For Permit 17121030 |
| Permit Number |
17121030 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2019-01-03 17:33:29 | MECHANICAL PROVISOS. | | | 1/3/18 | | | | | | 1) COMMISSIONING OF THE BREWERY OR DISTILLERY SYSTEM | | | SHALL BE PERFORMED BY A THIRD PARTY AGENCY (FL. | | | LICENSED ENGINEER OR FL. LICENSED MECHANICAL | | | CONTRACTOR), OR BY THE MANUFACTURER OF THE SYSTEM, AND | | | A LETTER OR REPORT CERTIFYING THE INSTALLATION AND | | | FUNCTIONING OF THE SYSTEM SHALL BE PROVIDED. THE LETTER | | | AND/OR REPORT SHALL BE REVIEWED AND APPROVED BY THE FL. | | | LICENSED ENGINEER OR ARCHITECT IN RESPONSIBLE CHARGE OF | | | THE PROJECT. | | | | | | 2) TEST AND BALANCE REPORT FOR THE HVAC SYSTEMS DUE AT | | | FINAL MECHANICAL INSPECTION. | | | | | | 3) DEFERRED SUBMITTALS: | | | | | | A) WIND LOAD ENGINEERING FOR INSTALLATION OF THE | | | OUTDOOR CHILLER ON THE WALL MOUNTED PLATFORM. | | | | | | B) GAS VENT PIPING, VENT TERMINATION CAP, AND VENT | | | SUPPORT STRAPS. | | | | | | |
|