Plan Review Notes
Plan Review Notes For Permit 17121030
Permit Number 17121030
Review Stop B
Sequence Number 4
Notes
Date Text
2019-01-10 18:39:002014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17121030
 ADD: 200 CLEMATIS ST. / 1ST FLOOR AND MEZZANINE.
 CONT: CONSTRUCTION TECHNOLOGIES
 TEL: 954-709-1935
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE & 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 PLAN
 REVIEW COMMENTS
 4TH REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 PLEASE COMPLY WITH: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY, COLATE PLANS INTO
 COMPLETE SETS. PLANS WILL NOT BE ISSUED IN PARTIAL
 SETS!!!!!!!!!!!
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 IT APPEARS THAT ALL OF THE ITEMS HAVE BEEN ADDRESSED
 EXCEPT FOR THE FOLLOWING ITEMS:
  
 1) THE WIND DESIGN DATA AND OPENING PRESSURES FOR THE
 NEW EXTERIOR DOOR OPENINGS WAS NOT ADDRESSED. THIS WILL
 BE ADDRESSED ALONG WITH THE REQUIRED PRODUCT APPROVALS
 ON A SEPARATE PERMIT FOR THE INSTALLATION OF THE NEW
 DOORS PER ARCHITECT'S RESPONSE LETTER. FBC 1603.1.4
  
 2) IT HAS BEEN BROUGHT TO MY ATTENTION THAT THE RAMP AT
 THE EXIT EGRESS DOOR ON THE EAST SIDE OF THE BUILDING
 WILL NOT BE REQUIRED. THE 2004 FBC ACCESSIBILITY
 SECTION 207.1 STATES THAT MEANS OF EGRESS SHALL COMPLY
 WITH 1003.2.13 OF THE 2000 EDITION OF THE INTERNATIONAL
 BUILDING CODE OR SECTION 1007 OF THE 2003 IBC. THESE
 SECTIONS HAVE AN EXCEPTION WHICH STATES THAT AN
 ACCESSIBLE MEANS OF EGRESS IS NOT REQUIRED IN
 ALTERATIONS TO EXISTING BUILDINGS. THEREFORE, THIS DOOR
 IS NOT BE REQUIRED TO HAVE A RAMP. PLEASE SUBMIT
 REVISED DRAWINGS THAT DO NOT SHOW THE RAMP. (THE RAMP
 THAT IS SHOWN EXTENDS BEYOND THE PROPERTY LINE AND THE
 LANDING WOULD NEED TO BE 60" WIDE DUE TO THE CHANGE IN
 DIRECTION.) FBC ACCESSIBILITY SECTION 405.7.4
  
 3) THE CALCULATIONS AND DRAWINGS THAT WERE SUBMITTED
 FOR THE VERTICAL TYPE B GAS VENTS LOCATED ON THE
 BUILDINGS EXTERIOR ADDRESSED THE WIND LOADS. HOWEVER,
 THE GRAVITY LOAD OF THE THESE VERTICAL GAS VENT PIPES
 WAS NOT ADDRESSED. SPECIFY THE TYPE OF CLAMPS THAT WILL
 BE USED AND HOW THEY WILL SUPPORT THE WEIGHT OF THE
 VERTICALLY INSTALLED VENTS. FBC 107.2.1.3
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
  
  
  