Plan Review Notes
Plan Review Notes For Permit 17121030
Permit Number 17121030
Review Stop M
Sequence Number 3
Notes
Date Text
2018-10-18 16:33:303RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17121030
 10/18/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 SOME OF THE COMMENTS FROM THE 1ST AND 2ND REVIEW HAVE
 NOT BEEN ADDRESSED COMPLETELY AND STILL EXIST. I HAVE
 REPRINTED THOSE COMMENTS BELOW, HOWEVER THE NUMERICAL
 AND ALPHABETICAL ORDERS HAVE CHANGED. OTHER COMMENTS
 THAT HAVE BEEN ADDRESSED HAVE BEEN DELETED. IN ORDER TO
 EXPEDITE REVIEW OF THE RESUBMITTED PLANS, PLEASE
 PROVIDE A RESPONSE NARRATIVE ADDRESSING EACH REMAINING
 AND EACH NEW COMMENT.
  
 1) THE MINIMUM VENTILATION CALCULATIONS FOR EXHAUST
 SYSTEMS WERE NOT PROVIDED. THERE IS A NEW EXHAUST FAN
 (EF-A) IN THE BREW TANK ROOM. PLEASE PROVIDE THE SIZING
 CALCULATIONS AND THE SEQUENCE OF OPERATION FOR THE FAN.
  
 2) THE REQUESTED CUT SHEET FOR THE NEW CHILLER WAS NOT
 PROVIDED- PLEASE PROVIDE.
  
 3) CUT SHEETS FOR THE BREW TANKS HAVE BEEN PROVIDED
 EACH INDICATING THAT THEY ARE PRESSURE VESSELS AND
 WOULD REQUIRE CERTIFICATION IN ACCORDANCE WITH THE ASME
 BOILER AND PRESSURE VESSEL CODE. THE CUT SHEETS DO NOT
 INDICATE THE TANKS HAVE THAT CERTIFICATION. PLEASE NOTE
 THAT HOT TANKS D AND E DO NOT LIST THE WORKING
 PRESSURES.
  
 4) THE REQUESTED WIND LOAD ENGINEERING FOR THE CHILLER
 WAS NOT PROVIDED. THE NEW NOTE ON S-2 INDICATES IT WILL
 BE DONE UNDER A SEPARATE PERMIT WHICH IS NOT
 ACCEPTABLE. PLEASE PROVIDE THE ENGINEERING OR REQUEST
 IT TO BE A DEFERRED SUBMITTAL.
  
 5) WORKING CLEARANCES AND ANCHORING DETAILS FOR THE
 BREW TANKS NOT PROVIDED.
  
 6) PROVIDE THE CLEARANCE DISTANCE FOR THE COMBUSTION
 AIR OPENING TO THE PROPERTY LINE, AND SUBMIT MIAMI-DADE
 NOA # 16-0201.08. PLEASE NOTE FL. PRODUCT APPROVAL
 #12941.1 IS NOT VALID FOR 2017.
  
 7) M-1: THE SUBMITTED MANUFACTURER SPECIFICATIONS FOR
 THE POWER FLAME EQUIPMENT BURNERS INDICATE THEY ARE TO
 BE ATTACHED IN SOME MANNER TO THE HOT LIQUOR AND BREW
 HOUSE TANKS EITHER DIRECTLY OR VIA A HEAT EXCHANGER.
 PLEASE PROVIDE A DETAIL SHOWING HOW THIS ATTACHMENT
 WILL BE MADE, AND HOW BY-PRODUCTS OF COMBUSTION WILL BE
 VENTED FROM THE TANKS OR THE EXHANGERS. THERE IS AN 8"
 VENT INDICATED FOR THE BREW HOUSE (E) ON SHEET M-2
 HOWEVER NO INFORMATION ON VENT SIZNG, VENT TYPE, OR
 VENT RUN WAS PROVIDED EITHER IN THE SPECS OR ON THE
 PLAN AS PREVIOOUSLY REQUESTED. PLEASE NOTE THAT NO VENT
 IS SHOWN FOR THE HOT LIQUOR TANK (D). PROVIDE A VENTING
 DIAGRAM THAT PROVIDES THE REQUESTED MISSING INFORMATION
 AND SUBMIT CUT SHEETS FOR THE VENT PIPE AND TERMINATION
 CAP- SEE SECTIONS 502, 503, AND 504 FBC FG.
  
 8) REFER TO SECTION 619.1 FBC FG AND VERIFY THAT THE
 POWER FLAME BURNERS CONFORM TO ANSI Z21.8.
  
 9) THERE IS A DISCREPANCY IN THE PLANS AND THE SPECS ON
 THE REQUIRED COMBUSTION AIR OPENING SIZING FOR THE
 POWER FLAME BURNERS. THE PLANS INDICATE 1 SQ. INCH PER
 3000 BTU/H, HOWEVER THE SPECS INDICATE 1/2 SQ. INCH PER
 1000 BTU/H. PROVIDE THE CORRECT CALCULATION AND OPENING
 SIZE PER THE MANUFACTURER'S SPECS. ADDITIONALLY PLEASE
 REFER TO SECTION 304.6.2 FBC FG FOR THE REQUIRED
 LOCATION OF THE OPENING TO COMMENCE WITHIN 12 INCHES OF
 THE TOP OF THE ENCLOSURE.
  
 10) SHEET M-2: IT IS NOT CLEAR IF AIR FROM THE NEW
 ENCLOSED BREWERY ROOM WILL BE RECIRCULATED TO THE
 OCCUPIED DINING AREAS, HOWEVER BASED ON TABLE 403.3.1.1
 RECIRCULATION OF AIR FROM KITCHEN COOKING AREAS IS
 PROHIBITIED, AND ALTHOUGH BREWERY AREAS ARE NOT LISTED
 IN THE TABLE, THE KITCHEN OCCUPANCY WOULD BE THE MOST
 SIMILAR- SEE SECTION 404.3.1.1 FOR AN EXPALNATION OF
 THIS.
  
 11) IN ACCORDANCE WITH SECTIONS 107.1 AND 107.2 WPB ALL
 EQUIPMENT AND APPLIANCE SUBMITTALS INCLUDING THE
 CHILLER AND BREW TANKS SHALL BEAR THE SHOP DRAWING
 STAMP OF THE EOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER