Plan Review Notes
Plan Review Notes For Permit 17121030
Permit Number 17121030
Review Stop P
Sequence Number 2
Notes
Date Text
2018-10-29 10:39:151) THE CHANNEL DRAIN SHALL BE EQUIPPED WITH A TRAP
 PRIMER. 2014 FBC-PLUMBING SEC.1002.4.
 2) SHT. A7.1 - ELEVATION "B" - THE TOILET PAPER
 DISPENSER SHALL BE LOCATED 7-9 INCHES TO THE CENTERLINE
 OF THE DISPENSER. 2014 FBC-ACCESS. SEC.604.7.
 3) SHT. A7.1 - ELEVATIONS A & B - THE HEIGHT OF THE
 GRAB BARS SHALL BE MEASURED TO THE TOP OF THE GRIPPING
 SURFACE. 2014 FBC-ACCESS. SEC. 609.4.
 4) THE MIRROR SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. 2014 FBC-ACCESS SEC. 603.3.
 5) SHT. P.5 - HOW IS THE HAND SINK ON THE 2ND FLOOR
 BEING VENTED? THE SANITARY RISER SHOWS IT AS AN "S"
 TRAP. CLARIFY.
 6) THE DRAIN FOR THE HAND SINK AND FLOOR SINK ON THE
 2ND FLOOR AND THE SINK ON THE FIRST FLOOR MUST CONNECT
 TO THE 1ST FLOOR HORIZONTAL DRAIN DOWNSTREAM OF THE
 BATHROOM GROUP. 2014 FBC-PLUMBING SEC.912.1.
 7) REMOVE ALL THE OLD PLUMBING SHEETS FROM THE PLAN
 SETS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW