Plan Review Notes
Plan Review Notes For Permit 17121030
Permit Number 17121030
Review Stop G
Sequence Number 2
Notes
Date Text
2018-10-29 09:26:32 
 1) CUT SHEETS FOR THE BREW TANKS HAVE BEEN PROVIDED
 EACH INDICATING THAT THEY ARE PRESSURE VESSELS AND
 WOULD REQUIRE CERTIFICATION IN ACCORDANCE WITH THE ASME
 BOILER AND PRESSURE VESSEL CODE. THE CUT SHEETS DO NOT
 INDICATE THE TANKS HAVE THAT CERTIFICATION. PLEASE NOTE
 THAT HOT TANKS D AND E DO NOT LIST THE WORKING
 PRESSURES.
  
 2) PROVIDE THE CLEARANCE DISTANCE FOR THE COMBUSTION
 AIR OPENING TO THE PROPERTY LINE.
  
 3) M-1: THE SUBMITTED MANUFACTURER SPECIFICATIONS FOR
 THE POWER FLAME EQUIPMENT BURNERS INDICATE THEY ARE TO
 BE ATTACHED IN SOME MANNER TO THE HOT LIQUOR AND BREW
 HOUSE TANKS EITHER DIRECTLY OR VIA A HEAT EXCHANGER.
 PLEASE PROVIDE A DETAIL SHOWING HOW THIS ATTACHMENT
 WILL BE MADE, AND HOW BY-PRODUCTS OF COMBUSTION WILL BE
 VENTED FROM THE TANKS OR THE EXHANGERS. THERE IS AN 8"
 VENT INDICATED FOR THE BREW HOUSE (E) ON SHEET M-2
 HOWEVER NO INFORMATION ON VENT SIZNG, VENT TYPE, OR
 VENT RUN WAS PROVIDED EITHER IN THE SPECS OR ON THE
 PLAN AS PREVIOOUSLY REQUESTED. PLEASE NOTE THAT NO VENT
 IS SHOWN FOR THE HOT LIQUOR TANK (D). PROVIDE A VENTING
 DIAGRAM THAT PROVIDES THE REQUESTED MISSING INFORMATION
 AND SUBMIT CUT SHEETS FOR THE VENT PIPE AND TERMINATION
 CAP- SEE SECTIONS 502, 503, AND 504 FBC FG. GAS VENTS
 SHALL TERMINATE IN ACCORDANCE WITH 2014 FBC-FUEL GAS
 SEC.
  
 4) REFER TO SECTION 619.1 FBC FG AND VERIFY THAT THE
 POWER FLAME BURNERS CONFORM TO ANSI Z21.8.
  
 5) THERE IS A DISCREPANCY IN THE PLANS AND THE SPECS ON
 THE REQUIRED COMBUSTION AIR OPENING SIZING FOR THE
 POWER FLAME BURNERS. THE PLANS INDICATE 1 SQ. INCH PER
 3000 BTU/H, HOWEVER THE SPECS INDICATE 1/2 SQ. INCH PER
 1000 BTU/H. PROVIDE THE CORRECT CALCULATION AND OPENING
 SIZE PER THE MANUFACTURER'S SPECS. ADDITIONALLY PLEASE
 REFER TO SECTION 304.6.2 FBC FG FOR THE REQUIRED
 LOCATION OF THE OPENING TO COMMENCE WITHIN 12 INCHES OF
 THE TOP OF THE ENCLOSURE.
  
 6) IN ACCORDANCE WITH SECTIONS 107.1 AND 107.2 WPB ALL
 EQUIPMENT AND APPLIANCE SUBMITTALS INCLUDING THE
 CHILLER AND BREW TANKS SHALL BEAR THE SHOP DRAWING
 STAMP OF THE EOR.
  
 7) THE REGULATOR VENTS FOR THE POWER FLAME BURNERS
 SHALL BE PIPED TO THE EXTERIOR PER 2014 FBC-FUEL GAS
 SEC.410.3. SEE EXCEPTION FOR VENT-LIMITING DEVICE.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LINE
 PRESSURE REGULATORS FOR THE POWER FLAME BURNERS. FBC
 SEC. 107.2.1.
  
 9) THERE IS ONLY ONE SHEET OF INFORMATION FOR TANK "E"
 AND IT IS JUST A PRODUCT SHEET. SUBMIT ADDITIONAL
 INFORMATION FOR THIS TANK.FBC 107.2.1.
  
 10) SHOW THE DISTANCE FROM THE LINE PRESSURE REGULATORS
 TO THE POWER FLAME BURNERS.
  
 11) COMPLETE PIPING PLANS SHALL BE PROVIDED FOR ALL THE
 TANKS. FBC 107.2.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  