| Date |
Text |
| 2018-02-08 11:37:53 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17121030 |
| | ADD: 200 CLEMATIS ST./ 1ST FLOOR AND MEZZANINE. |
| | CONT: RISKAS CONSTRUCTION CORP. |
| | TEL: 561-588-5455 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. FEB. 08/ 2018 |
| | ACTION: DENIED |
| | |
| | PLEASE: WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1) THE COVERSHEET LIST THE OF DRAWINGS INDICATES THERE |
| | ARE NO MECHANICAL, PLUMBING, ELECTRICAL, PLANS TO BE |
| | UNDER SEPARATE PERMIT. PLEASE NOTE THE SCOPE OF THE |
| | WHOLE PROJECT IS INTERRELATED WITH ALL TRADES. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... THE ARCHITECT OF RECORD WILL NEED |
| | TO COORDINATE TRADES, AND MATERIALS. THERE HAS TO BE A |
| | PROFESSIONAL DESIGNER OVER ALL OF THE PROJECT. |
| | |
| | 1A) COMPLIED. ENGINEERING PLANS AND CALCULATIONS. |
| | |
| | 1B) BUILDING PROVISO. 106.1 LIVE LOADS POSTED. WHERE |
| | THE LIVE LOADS FOR WHICH EACH FLOOR OR PORTION THEREOF |
| | OF A COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN |
| | DESIGNED TO EXCEED 50 PSF, SUCH DESIGN LIVE LOADS SHALL |
| | BE CONSPICUOUSLY POSTED BY THE OWNER IN THAT PART OF |
| | EACH STORY IN WHICH THEY APPLY, USING DURABLE SIGNS. IT |
| | SHALL BE UNLAWFUL TO REMOVE OR DEFACE SUCH NOTICES |
| | |
| | 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A |
| | CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111 SHALL |
| | NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS, REQUIRED BY |
| | SECTION 106.1, HAVE BEEN INSTALLED. |
| | |
| | 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL TO |
| | PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON ANY FLOOR OR |
| | ROOF OF A BUILDING, STRUCTURE OR PORTION THEREOF, A |
| | LOAD GREATER THAN IS PERMITTED BY THIS CODE. |
| | |
| | 2014 FBC-B 1607.4 CONCENTRATED LIVE LOADS. FLOORS AND |
| | OTHER SIMILAR SURFACES SHALL BE DESIGNED TO SUPPORT THE |
| | UNIFORMLY DISTRIBUTED LIVE LOADS PRESCRIBED IN SECTION |
| | 1607.3 OR THE CONCENTRATED LIVE LOADS GIVEN IN TABLE |
| | 1607.1, WHICHEVER PRODUCES THE GREATER LOAD EFFECTS. |
| | UNLESS OTHERWISE SPECIFIED, THE INDICATED CONCENTRATION |
| | SHALL BE ASSUMED TO BE UNIFORMLY DISTRIBUTED OVER AN |
| | AREA OF 21/2 FEET BY 21/2 FEET (762 MM BY 762 MM) AND |
| | SHALL BE LOCATED SO AS TO PRODUCE THE MAXIMUM LOAD |
| | EFFECTS IN THE STRUCTURAL MEMBERS. |
| | |
| | 1607.2 LOADS NOT SPECIFIED. |
| | FOR OCCUPANCIES OR USES NOT DESIGNATED IN TABLE 1607.1, |
| | THE LIVE LOAD SHALL BE DETERMINED IN ACCORDANCE WITH A |
| | METHOD APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 2) 2ND REQUEST. SHEET A4.0 INDICATES THERE WILL BE |
| | STRUCTURAL PLANS TO FOLLOW. PLEASE BE AWARE THAT WITH |
| | THIS BEING A 8 STORY BUILDING THIS BY DEFINITION A |
| | THRESHOLD BUILDING AND MEETING THESE REQUIREMENTS: |
| | THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN. |
| | THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) 2ND REQUEST: THRESHOLD INSPECTOR: WPB AMENDMENT |
| | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE |
| | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT |
| | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO |
| | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT |
| | ISSUANCE WILL TAKE PLACE. |
| | FORMS E-MAILED: [email protected] |
| | SENT: 02/08/2018 10:38 AM |
| | |
| | 2C) 2ND REQUEST. THRESHOLD BLDG., REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE |
| | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. |
| | |
| | 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 2F) 2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF |
| | DOCUMENTS ARE REQUIRED. 2014 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 110.3.7 THRESHOLD BUILDINGS, GUIDELINES |
| | AND POLICIES FOR PROJECTS CONCERNING SPECIAL |
| | INSPECTORS. |
| | |
| | 2G) 2ND REQUEST. 110.3.7.4.3 ALL SHORING AND RESHORING |
| | PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE |
| | ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND |
| | RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED |
| | AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 2H) 2ND REQUEST. PLEASE CALL THE CITY OF WEST PALM |
| | BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN |
| | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | I) 2ND REQUEST. 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| | THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 3) 2ND REQUEST. SHEET A-4 INDICATES A NEW POLISHED |
| | CONCRETE SLAB THE A-4 SHEET DOESN?T INDICATE ANY WIRE |
| | MESH OR STEEL IN THE SLAB. THE STRUCTURAL SHEET S-2 |
| | DETAIL 2 SHOWS THE STRUCTURAL STEEL FOR THE 2ND FLOOR |
| | AND 3 DETAILS ON S3 DETAILS A, B & C. ALL 3 OF THESE |
| | DETAILS SHOW THE NEW STEEL FRAME WORK TO BE INSTALLED |
| | BENEATH THE 2ND FLOOR. THE PLAN SHOWS THE STRUCTURAL |
| | SLAB, NO TOPPING OF 4 TO 5 INCHES? SHEET A2.1 IN THE |
| | BOTTOM LEFT CORNER OF THE PLAN HAS A NOTE THIS AREA TO |
| | BE REINFORCED BY A STRUCTURAL ENGINEER. ENGINEERING |
| | PLANS ARE TO BE SUBMITTED FOR APPROVAL. PLEASE NOTE |
| | THERE IS NO SHOP DRAWING STAMP REVIEWED BY THE |
| | ARCHITECT OF RECORD. |
| | |
| | 1ST ROUND OF COMMENTS. SHEET A4.0 SHOWS THE 2ND FLOOR |
| | IN THE AREA OF THE NEW TANKS ARE TO BE LOCATED, THE |
| | FLOOR BEING RAISED 5 INCHES AND A LINEAR FLOOR DRAIN, |
| | THE PLANS ARE SILENT, NO DETAILS FOR THE RAISED FLOOR |
| | FRAMING, DECKING OR FINISH MATERIAL NOR FLOOR DRAIN |
| | MATERIAL? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4) 2ND REQUEST. THE PLANS INDICATE THIS IS A NEW |
| | BREWERY BUT THE PLANS ARE SILENT AS TO THE ALCOHOL |
| | CONTENT. PLEASE NOTE WHEN THE BEVERAGES HAVE AN ALCOHOL |
| | CONTENT OF OVER 16 PER CENT THEN THE BREWERY WOULD BE |
| | CLASSIFIED AS AN F1 OCCUPANCY AND OCCUPANCY SEPARATION |
| | MAY BE REQUIRED. SEE FBC-B TABLE 508.4. ONE HOUR |
| | REDUCTION FOR SPRINKLERED BUILDINGS. |
| | |
| | 5) 2ND REQUEST. QUESTION, DOESN?T ALL BREWERIES REQUIRE |
| | A BOILER AND 1 HOUR RATED ROOM. THE PLANS DO NOT SHOW |
| | THE BOILER NOR SIZE? PLEASE REVIEW THE 2014 FBC-B TABLE |
| | 509. ROOMS WITH BOILERS WHERE THE LARGEST PIECE OF |
| | EQUIPMENT IS OVER 15 PSI AND 10 HORSEPOWER WOULD |
| | REQUIRE 1 HOUR SEPARATION OR AUTOMATIC SPRINKLERS |
| | SYSTEM. |
| | |
| | 6) SEMI- COMPLIED SEE COMMENT # 7. SHEETS A.1 AND A3.0 |
| | BOTH SHOW A NEW BAR SYSTEM ON THE EAST SIDE OF THE |
| | BUILDING. PLEASE PROVIDE A WALL DETAIL OF THE INFILL |
| | WALL AND DOOR/ WINDOW SYSTEM. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1.1. COMMERCIAL BUILDINGS: BUILDING. |
| | 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | BUILDING ENVELOPE |
| | WIND REQUIREMENTS |
| | |
| | 7) SEMI-COMPLIED. 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING. 1609.3.1 WIND SPEED CONVERSION |
| | VULT TO VASD. |
| | |
| | 8) 2ND REQUEST. 2014 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS , |
| | (B) WINDOWS |
| | ( C ) MECHANICAL EQUIPMENT STAND WALL MOUNT SHEETS A1, |
| | A3 & A4 ALL REFER TO THE ENGINEERING PLAN. NOTHING FOR |
| | A MECHANICAL WALL MOUNT STAND IN THE STRUCTURAL PLANS |
| | OR M1 PLAN. |
| | |
| | 9) 2ND REQUEST. W. P. B. 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 10) 2ND REQUEST. SHEET A1.0 INDICATES THERE ARE 180 |
| | INDOOR SEATS AND THE PLAN SHOWS 84 EXTERIOR SEATS WITH |
| | A TOTAL OF 264 SEATS. THE ACCESSIBILITY CODE REQUIRES |
| | 0.05 % OF ALL SEATING TO BE ACCESSIBLE. 13.2 OR 14 |
| | SEATS ALWAYS ROUND UP. 226.1 WHERE DINING SURFACES ARE |
| | PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST |
| | 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT |
| | THE DINING SURFACES SHALL COMPLY WITH 902. |
| | |
| | 11) SEMI-COMPLIED. SHEET A-4.0 SHOWS A ACCESSIBLE BAR |
| | SECTION FOR THE INTERIOR BARS BUT NOT THE EXTERIOR |
| | BARS. 226.2 DISPERSION. DINING SURFACES AND WORK |
| | SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 12) 2ND REQUEST. 902.1 .DINING SURFACES AND WORK |
| | SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY |
| | 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT |
| | LIMITED TO, BARS, INCLUDING THE EXTERIOR BAR, TABLES, |
| | LUNCH COUNTERS, AND BOOTHS. |
| | |
| | 13)(A) 2ND REQUEST. 902.2 CLEAR FLOOR OR GROUND SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A |
| | FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE |
| | CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 13)(B)2ND REQUEST. 902.3 HEIGHT. THE TOPS OF DINING |
| | SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM |
| | AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 14A-B) COMPLIED. |
| | |
| | 14C) 2ND REQUEST. SHEET A4.0 2014 FBC-B 1008.1.10 PANIC |
| | AND FIRE EXIT HARDWARE. DOORS SERVING ROOMS OR SPACES |
| | WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A |
| | OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR LOCK |
| | UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |