2018-02-06 15:50:381ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE FIXTURES IN THE NEW BAR AREA SHOULD NOT BE
 CONNECTED TO THE GREASE WASTE UNLESS FOOD PREP OR
 COOKING IS BEING DONE IN THIS AREA. FIXTURES THAT DON'T
 PRODUCE GREASY WASTE SHALL NOT DISCHARGE TO GREASE
 INTERCEPTOR, OR PROVIDE SIZING CALCULATIONS WITH NEW
 GREASE WASTE LOAD. PER FBC PL 1003.3.1
  
 2. THE NEW HAND SINK ON SECOND LEVEL SHALL BE PROVIDED
 WITH HOT WATER. PER FBC PL 607.1
  
 3. THE FLOOR DRAIN ON THE SECOND LEVEL IS SHOWN AS 3"
 ON THE ISOMETRIC DRAWING THE BRANCH DRAIN CONNECTED TO
 IT IS SHOWN AS 2" A PIPE CAN NOT DECREASE IN SIZE IN
 THE DIRECTION OF FLOW.PER FBC PL 704.2
  
 4. A TRAP PRIMER IS REQUIRED ON THE FLOOR DRAINS . PER
 FBC PL 1002.4
  
 5. PLEASE PROVIDE A RISER DIAGRAM FOR ALL PROCESS
 PIPING FOR BREWING. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 6. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE BREWING
 EQUIPMENT. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  