| 2018-01-29 08:36:31 | 1ST REVIEW FBC-2014 MECHANICAL & EXISTING BUILDING |
| | CODES, WPB AMENDMENTS TO THE FBC. |
| | PERMIT #17121030 |
| | 1/29/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET CS: THE ARCHITECT OF RECORD HAS PROVIDED |
| | CONFUSING INFORMATION ON THE PLANS REGARDING THE |
| | PERMITTING OF THE MECHANICAL WORK ON THE PROJECT. THE |
| | ARCHITECT STATES THAT MEP SHEETS ARE ATTACHED BUT THEN |
| | HAS A NOTE STATING "UNDER SEPARATE PERMIT". THAT NOTE |
| | APPEARS TO BE IN CONFLICT WITH THE SCOPE OF WORK NOTES |
| | WHICH INDICATE NEW DUCTWORK AND RELOCATION OF |
| | |
| | DUCTWORK. CURRENTLY NO MECHANICAL PLANS OR |
| | SPECIFICATIONS HAVE BEEN SUBMITTED FOR REVIEW. |
| | |
| | REFER TO SECTION 107.3.5.1.4 AND REVIEW THE MINIMUM |
| | MECHANICAL PLAN REVIEW CRITERIA REQUIRED FOR |
| | PERMITTING. PERTAINING TO THE PROPOSED PROJECT PLEASE |
| | PROVIDE COMPLETE MECHANICAL PLANS UNDER THIS PERMIT, OR |
| | SEPARATE PERMIT, INCLUDING BUT NOT LIMITED TO: |
| | |
| | A) DUCT LAYOUT DRAWINGS THAT SHOW ALL NEW AND RELOCATED |
| | DUCTS, DIFFUSERS, GRILLS, FIRE DAMPERS, DUCT SMOKE |
| | DETECTORS ETC. |
| | |
| | B) AIR DEVICE SCHEDULE |
| | |
| | C) DUCT HANGING, CONNECTION, AND SUPPORT DETAILS |
| | |
| | B) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND |
| | SPACES |
| | |
| | D) MINIMUM VENTILATION CALCULATIONS FOR EXHAUST SYSTEMS |
| | |
| | E) COOLING AND HEATING LOAD CALCULATIONS FOR ALL NEW AC |
| | SYSTEMS |
| | |
| | F) COMBUSTION AIR CALCULATIONS FOR ALL GAS-FIRED |
| | EQUIPMENT |
| | |
| | G) EQUIPMENT SCHEDULES AND CUT SHEETS FOR THE BREW |
| | TANKS, CHILLER, BOILER, FLUE VENTS, REFRIGERATION, |
| | APPLIANCES ETC. |
| | |
| | H) CHILLER WATER AND STEAM PIPING LAYOUT PLANS AND |
| | SPECIFICATIONS. |
| | |
| | I) WORKING CLEARANCES FOR EQUIPMENT AND ACCESS FOR |
| | SERVICE AND REPLACEMENT. |
| | |
| | J) EQUIPMENT ANCHORING DETAILS |
| | |
| | K) WIND LOAD ENGINEERING FOR ALL EXTERIOR MOUNTED |
| | APPLIANCES AND EQUIPMENT. |
| | |
| | L) OUTDOOR AIR INLET AND EXHAUST OUTLET LOCATIONS, |
| | CLEARANCES AND OPENING PROTECTIONS. |
| | |
| | 2) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN |
| | HOODS, FIRE SUPPRESSION, AND WALK-IN COOLERS AND |
| | FREEZERS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |