Plan Review Notes
Plan Review Notes For Permit 17121030
Permit Number 17121030
Review Stop M
Sequence Number 1
Notes
Date Text
2018-01-29 08:36:311ST REVIEW FBC-2014 MECHANICAL & EXISTING BUILDING
 CODES, WPB AMENDMENTS TO THE FBC.
 PERMIT #17121030
 1/29/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET CS: THE ARCHITECT OF RECORD HAS PROVIDED
 CONFUSING INFORMATION ON THE PLANS REGARDING THE
 PERMITTING OF THE MECHANICAL WORK ON THE PROJECT. THE
 ARCHITECT STATES THAT MEP SHEETS ARE ATTACHED BUT THEN
 HAS A NOTE STATING "UNDER SEPARATE PERMIT". THAT NOTE
 APPEARS TO BE IN CONFLICT WITH THE SCOPE OF WORK NOTES
 WHICH INDICATE NEW DUCTWORK AND RELOCATION OF
  
 DUCTWORK. CURRENTLY NO MECHANICAL PLANS OR
 SPECIFICATIONS HAVE BEEN SUBMITTED FOR REVIEW.
  
 REFER TO SECTION 107.3.5.1.4 AND REVIEW THE MINIMUM
 MECHANICAL PLAN REVIEW CRITERIA REQUIRED FOR
 PERMITTING. PERTAINING TO THE PROPOSED PROJECT PLEASE
 PROVIDE COMPLETE MECHANICAL PLANS UNDER THIS PERMIT, OR
 SEPARATE PERMIT, INCLUDING BUT NOT LIMITED TO:
  
 A) DUCT LAYOUT DRAWINGS THAT SHOW ALL NEW AND RELOCATED
 DUCTS, DIFFUSERS, GRILLS, FIRE DAMPERS, DUCT SMOKE
 DETECTORS ETC.
  
 B) AIR DEVICE SCHEDULE
  
 C) DUCT HANGING, CONNECTION, AND SUPPORT DETAILS
  
 B) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES
  
 D) MINIMUM VENTILATION CALCULATIONS FOR EXHAUST SYSTEMS
  
 E) COOLING AND HEATING LOAD CALCULATIONS FOR ALL NEW AC
 SYSTEMS
  
 F) COMBUSTION AIR CALCULATIONS FOR ALL GAS-FIRED
 EQUIPMENT
  
 G) EQUIPMENT SCHEDULES AND CUT SHEETS FOR THE BREW
 TANKS, CHILLER, BOILER, FLUE VENTS, REFRIGERATION,
 APPLIANCES ETC.
  
 H) CHILLER WATER AND STEAM PIPING LAYOUT PLANS AND
 SPECIFICATIONS.
  
 I) WORKING CLEARANCES FOR EQUIPMENT AND ACCESS FOR
 SERVICE AND REPLACEMENT.
  
 J) EQUIPMENT ANCHORING DETAILS
  
 K) WIND LOAD ENGINEERING FOR ALL EXTERIOR MOUNTED
 APPLIANCES AND EQUIPMENT.
  
 L) OUTDOOR AIR INLET AND EXHAUST OUTLET LOCATIONS,
 CLEARANCES AND OPENING PROTECTIONS.
  
 2) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN
 HOODS, FIRE SUPPRESSION, AND WALK-IN COOLERS AND
 FREEZERS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  