Plan Review Notes
Plan Review Notes For Permit 17121030
Permit Number 17121030
Review Stop E
Sequence Number 1
Notes
Date Text
2018-02-02 15:15:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. MANY AREAS OF THE PLAN ARE SO LIGHT AS TO BE
 UNREADABLE. PROVIDE PLANS IN LINE WITH THE WEST PALM
 BEACH AMENDMENTS TO THE FBC: 107.2.1.4 QUALITY OF
 BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR
 OTHER ACCEPTABLE MEDIUM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. FBC 107.2.1
 2. PLAN SHOWS THE 1000 AMP FEED AS (4)400 KCMIL AND A
 2/0 IN AN EXISTING 2 ? CONDUIT. THE TOTAL AREA OF THESE
 WIRES EXCEEDS THE ALLOWABLE SPACE OF 2 ? CONDUIT, SO A
 LARGER SIZE CONDUIT IS REQUIRED. PROVIDE CORRECTION.
 NEC CHAPTER 9, TABLE 2 AND 4.
 3. PLAN SHOWS AN EXISTING 1000 AMP PANEL THAT HAS AN
 800 AMP DISCONNECT BEING CHANGED TO A 1000 AMP
 DISCONNECT FOR NEW FEED. PROVIDE LOAD CALCULATION FOR
 THIS SERVICE TO CONFIRM THE CAPACITY OF THIS IS
 ADEQUATE FOR THE ADDITIONAL LOAD. LOAD CALCULATION
 SHOULD SHOW THE PROPER DEMAND FACTORS, INCLUDING 100%
 OF THE NON-CONTINUOUS LOAD AND 125% OF THE CONTINUOUS
 LOAD FOR SIZING OF FEEDERS. NEC 215.2, 220, 408.30; FBC
 107.2.1
 4. PROVIDE LOAD CALCULATION OF NEW PANELS BEING ADDED
 TO CONFIRM FEEDER AND OCP IS SIZED PROPERLY. NEC 215.2,
 220, 408.30; FBC 107.2.1
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 6. INDICATE WIRE SIZES ON PLAN FOR ANY CIRCUITS TO BE
 INSTALLED. NEC 215.2, 310.15(B)(16); FBC 107.2.1
 7. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  