| 2018-01-12 13:58:46 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17121030 |
| | ADD: 200 CLEMATIS ST./ 1ST FLOOR AND MEZZANINE. |
| | CONT: RISKAS CONSTRUCTION CORP. |
| | TEL: 561-588-5455 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JAN. 12/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET LIST THE OF DRAWINGS INDICATES THERE |
| | ARE NO MECHANICAL, PLUMBING, ELECTRICAL, PLANS TO BE |
| | UNDER SEPARATE PERMIT. PLEASE NOTE THE SCOPE OF THE |
| | WHOLE PROJECT IS INTERRELATED WITH ALL TRADES. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... THE ARCHITECT OF RECORD WILL NEED |
| | TO COORDINATE TRADES, AND MATERIALS. THERE HAS TO BE A |
| | PROFESSIONAL DESIGNER OVER ALL OF THE PROJECT. |
| | |
| | 2A) SHEET A-4 INDICATES THERE WILL BE FUTURE |
| | ENGINEERING PLANS BUT THERE ARE NO ENGINEERING SHEETS |
| | IN THIS SET OF PLANS. TERMS THAT NEED TO BE DEFINED IS: |
| | BBL/ BARREL PLEASE PROVIDE THE GALLONS IN U. S. GALLONS |
| | AND WEIGHT FOR 5BBL, 10 BBL & 20 BBL. FOR THIS REVIEW I |
| | WILL USE 50 GALLONS = 1 BARREL. |
| | |
| | TANK SIZES ARE AS FOLLOWS (ASSUMED) : |
| | |
| | 5 BBL 5X50GAL/ BBL= 250 GAL, 250 X 8.34 LBS/ GAL= 2,000 |
| | LBS. + TANK WEIGHT |
| | 10 BBL 10 X50GAL/BBL= 500 GAL. 500X 8.34 LBS/ GAL = |
| | 4,170 LBS. + TANK WEIGHT |
| | 20 BBL 20X50 GAL/BBL= 1000 GAL. 1000X 8.34 LBS/ GAL = |
| | 8,340 LBS. + TANK WEIGHT |
| | |
| | PLEASE PROVIDE THE ACTUAL WEIGHT THAT WILL BE ADDING TO |
| | THE EXISTING FLOOR. |
| | |
| | 2B) 106.1 LIVE LOADS POSTED. WHERE THE LIVE LOADS FOR |
| | WHICH EACH FLOOR OR PORTION THEREOF OF A COMMERCIAL OR |
| | INDUSTRIAL BUILDING IS OR HAS BEEN DESIGNED TO EXCEED |
| | 50 PSF, SUCH DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY |
| | POSTED BY THE OWNER IN THAT PART OF EACH STORY IN WHICH |
| | THEY APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL |
| | TO REMOVE OR DEFACE SUCH NOTICES |
| | |
| | 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A |
| | CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111 SHALL |
| | NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS, REQUIRED BY |
| | SECTION 106.1, HAVE BEEN INSTALLED. |
| | |
| | 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL TO |
| | PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON ANY FLOOR OR |
| | ROOF OF A BUILDING, STRUCTURE OR PORTION THEREOF, A |
| | LOAD GREATER THAN IS PERMITTED BY THIS CODE. |
| | |
| | 2014 FBC-B 1607.4 CONCENTRATED LIVE LOADS. FLOORS AND |
| | OTHER SIMILAR SURFACES SHALL BE DESIGNED TO SUPPORT THE |
| | UNIFORMLY DISTRIBUTED LIVE LOADS PRESCRIBED IN SECTION |
| | 1607.3 OR THE CONCENTRATED LIVE LOADS GIVEN IN TABLE |
| | 1607.1, WHICHEVER PRODUCES THE GREATER LOAD EFFECTS. |
| | UNLESS OTHERWISE SPECIFIED, THE INDICATED CONCENTRATION |
| | SHALL BE ASSUMED TO BE UNIFORMLY DISTRIBUTED OVER AN |
| | AREA OF 21/2 FEET BY 21/2 FEET (762 MM BY 762 MM) AND |
| | SHALL BE LOCATED SO AS TO PRODUCE THE MAXIMUM LOAD |
| | EFFECTS IN THE STRUCTURAL MEMBERS. |
| | |
| | 1607.2 LOADS NOT SPECIFIED. |
| | FOR OCCUPANCIES OR USES NOT DESIGNATED IN TABLE 1607.1, |
| | THE LIVE LOAD SHALL BE DETERMINED IN ACCORDANCE WITH A |
| | METHOD APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 2) SHEET A4.0 INDICATES THERE WILL BE STRUCTURAL PLANS |
| | TO FOLLOW. PLEASE BE AWARE THAT WITH THIS BEING A 8 |
| | STORY BUILDING THIS BY DEFINITION A THRESHOLD BUILDING |
| | AND MEETING THESE REQUIREMENTS: |
| | THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. |
| | FORMS E-MAILED: |
| | |
| | 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 110.3.7 THRESHOLD BUILDINGS, GUIDELINES AND POLICIES |
| | FOR PROJECTS CONCERNING SPECIAL INSPECTORS. |
| | |
| | 2G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 3) SHEET A4.0 SHOWS THE 2ND FLOOR IN THE AREA OF THE |
| | NEW TANKS ARE TO BE LOCATED, THE FLOOR BEING RAISED 5 |
| | INCHES AND A LINEAR FLOOR DRAIN, THE PLANS ARE SILENT, |
| | NO DETAILS FOR THE RAISED FLOOR FRAMING, DECKING OR |
| | FINISH MATERIAL NOR FLOOR DRAIN MATERIAL? 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4) THE PLANS INDICATE THIS IS A NEW BREWERY BUT THE |
| | PLANS ARE SILENT AS TO THE ALCOHOL CONTENT. PLEASE NOTE |
| | WHEN THE BEVERAGES HAVE AN ALCOHOL CONTENT OF OVER 16 |
| | PER CENT THEN THE BREWERY WOULD BE CLASSIFIED AS AN F1 |
| | OCCUPANCY AND OCCUPANCY SEPARATION MAY BE REQUIRED. SEE |
| | FBC-B TABLE 508.4. ONE HOUR REDUCTION FOR SPRINKLERED |
| | BUILDINGS. |
| | |
| | 5) QUESTION, DOESN?T ALL BREWERIES REQUIRE A BOILER AND |
| | 1 HOUR RATED ROOM. THE PLANS DO NOT SHOW THE BOILER NOR |
| | SIZE? PLEASE REVIEW THE 2014 FBC-B TABLE 509. ROOMS |
| | WITH BOILERS WHERE THE LARGEST PIECE OF EQUIPMENT IS |
| | OVER 15 PSI AND 10 HORSEPOWER WOULD REQUIRE 1 HOUR |
| | SEPARATION OR AUTOMATIC SPRINKLERS SYSTEM. |
| | |
| | 6) SHEETS A.1 AND A3.0 BOTH SHOW A NEW BAR SYSTEM ON |
| | THE EAST SIDE OF THE BUILDING. PLEASE PROVIDE A WALL |
| | DETAIL OF THE INFILL WALL AND DOOR/ WINDOW SYSTEM. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1.1. COMMERCIAL BUILDINGS: BUILDING. |
| | 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | BUILDING ENVELOPE |
| | WIND REQUIREMENTS |
| | |
| | 7) MISSING THE WIND DESIGN. PLEASE NOTE THE NEGATIVE |
| | PRESSURES ARE TAKEN FROM THE ROOF. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 7.2. RISK CATEGORY. |
| | |
| | 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 8) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS , |
| | (B) WINDOWS |
| | ( C ) MECHANICAL EQUIPMENT STAND WALL MOUNT |
| | |
| | 9) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 10) SHEET A1.0 INDICATES THERE ARE 180 INDOOR SEATS AND |
| | THE PLAN SHOWS 84 EXTERIOR SEATS WITH A TOTAL |
| | 264 SEATS. THE ACCESSIBILITY CODE REQUIRES 0.05 % OF |
| | ALL SEATING TO BE ACCESSIBLE. 13.2 OR 14 SEATS ALWAYS |
| | ROUND UP. 226.1 WHERE DINING SURFACES ARE PROVIDED FOR |
| | THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF |
| | THE SEATING SPACES AND STANDING SPACES AT THE DINING |
| | SURFACES SHALL COMPLY WITH 902. |
| | |
| | 11) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 12) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | INCLUDING THE EXTERIOR BAR, TABLES, LUNCH COUNTERS, AND |
| | BOOTHS. |
| | |
| | 13)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 13)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 14) SHEET A2.1 THE UPSTAIRS SHOWS A NEW FIRE RATED EXIT |
| | DOOR. NO NOTATION AS TO THE SIZE OF DOOR OR HARDWARE |
| | FOR THE FIRE RATED DOOR. |
| | |
| | 14A) 2014 FBC-B TABLE 716.5 OPENING PROTECTIVES. |
| | |
| | 14B) 2014 FBC-B 1008.1.1 SIZE OF DOORS. THE MINIMUM |
| | WIDTH OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE |
| | OCCUPANT LOAD THEREOF AND SHALL PROVIDE A CLEAR WIDTH |
| | OF 32 INCHES (813 MM). CLEAR OPENINGS OF DOORWAYS WITH |
| | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF |
| | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. |
| | |
| | 14C) 2014 FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE. |
| | DOORS SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF |
| | 50 OR MORE IN A GROUP A OCCUPANCY SHALL NOT BE PROVIDED |
| | WITH A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR |
| | FIRE EXIT HARDWARE. |
| | |
| | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |