Plan Review Notes
Plan Review Notes For Permit 17121030
Permit Number 17121030
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-12 13:58:462014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17121030
 ADD: 200 CLEMATIS ST./ 1ST FLOOR AND MEZZANINE.
 CONT: RISKAS CONSTRUCTION CORP.
 TEL: 561-588-5455
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 12/ 2018
 ACTION: DENIED
  
 1) THE COVERSHEET LIST THE OF DRAWINGS INDICATES THERE
 ARE NO MECHANICAL, PLUMBING, ELECTRICAL, PLANS TO BE
 UNDER SEPARATE PERMIT. PLEASE NOTE THE SCOPE OF THE
 WHOLE PROJECT IS INTERRELATED WITH ALL TRADES.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC... THE ARCHITECT OF RECORD WILL NEED
 TO COORDINATE TRADES, AND MATERIALS. THERE HAS TO BE A
 PROFESSIONAL DESIGNER OVER ALL OF THE PROJECT.
  
 2A) SHEET A-4 INDICATES THERE WILL BE FUTURE
 ENGINEERING PLANS BUT THERE ARE NO ENGINEERING SHEETS
 IN THIS SET OF PLANS. TERMS THAT NEED TO BE DEFINED IS:
 BBL/ BARREL PLEASE PROVIDE THE GALLONS IN U. S. GALLONS
 AND WEIGHT FOR 5BBL, 10 BBL & 20 BBL. FOR THIS REVIEW I
 WILL USE 50 GALLONS = 1 BARREL.
  
 TANK SIZES ARE AS FOLLOWS (ASSUMED) :
  
 5 BBL 5X50GAL/ BBL= 250 GAL, 250 X 8.34 LBS/ GAL= 2,000
 LBS. + TANK WEIGHT
 10 BBL 10 X50GAL/BBL= 500 GAL. 500X 8.34 LBS/ GAL =
 4,170 LBS. + TANK WEIGHT
 20 BBL 20X50 GAL/BBL= 1000 GAL. 1000X 8.34 LBS/ GAL =
 8,340 LBS. + TANK WEIGHT
  
 PLEASE PROVIDE THE ACTUAL WEIGHT THAT WILL BE ADDING TO
 THE EXISTING FLOOR.
  
 2B) 106.1 LIVE LOADS POSTED. WHERE THE LIVE LOADS FOR
 WHICH EACH FLOOR OR PORTION THEREOF OF A COMMERCIAL OR
 INDUSTRIAL BUILDING IS OR HAS BEEN DESIGNED TO EXCEED
 50 PSF, SUCH DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY
 POSTED BY THE OWNER IN THAT PART OF EACH STORY IN WHICH
 THEY APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL
 TO REMOVE OR DEFACE SUCH NOTICES
  
 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A
 CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111 SHALL
 NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS, REQUIRED BY
 SECTION 106.1, HAVE BEEN INSTALLED.
  
 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL TO
 PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON ANY FLOOR OR
 ROOF OF A BUILDING, STRUCTURE OR PORTION THEREOF, A
 LOAD GREATER THAN IS PERMITTED BY THIS CODE.
  
 2014 FBC-B 1607.4 CONCENTRATED LIVE LOADS. FLOORS AND
 OTHER SIMILAR SURFACES SHALL BE DESIGNED TO SUPPORT THE
 UNIFORMLY DISTRIBUTED LIVE LOADS PRESCRIBED IN SECTION
 1607.3 OR THE CONCENTRATED LIVE LOADS GIVEN IN TABLE
 1607.1, WHICHEVER PRODUCES THE GREATER LOAD EFFECTS.
 UNLESS OTHERWISE SPECIFIED, THE INDICATED CONCENTRATION
 SHALL BE ASSUMED TO BE UNIFORMLY DISTRIBUTED OVER AN
 AREA OF 21/2 FEET BY 21/2 FEET (762 MM BY 762 MM) AND
 SHALL BE LOCATED SO AS TO PRODUCE THE MAXIMUM LOAD
 EFFECTS IN THE STRUCTURAL MEMBERS.
  
 1607.2 LOADS NOT SPECIFIED.
 FOR OCCUPANCIES OR USES NOT DESIGNATED IN TABLE 1607.1,
 THE LIVE LOAD SHALL BE DETERMINED IN ACCORDANCE WITH A
 METHOD APPROVED BY THE BUILDING OFFICIAL.
  
 2) SHEET A4.0 INDICATES THERE WILL BE STRUCTURAL PLANS
 TO FOLLOW. PLEASE BE AWARE THAT WITH THIS BEING A 8
 STORY BUILDING THIS BY DEFINITION A THRESHOLD BUILDING
 AND MEETING THESE REQUIREMENTS:
 THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
 FORMS E-MAILED:
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 110.3.7 THRESHOLD BUILDINGS, GUIDELINES AND POLICIES
 FOR PROJECTS CONCERNING SPECIAL INSPECTORS.
  
 2G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 3) SHEET A4.0 SHOWS THE 2ND FLOOR IN THE AREA OF THE
 NEW TANKS ARE TO BE LOCATED, THE FLOOR BEING RAISED 5
 INCHES AND A LINEAR FLOOR DRAIN, THE PLANS ARE SILENT,
 NO DETAILS FOR THE RAISED FLOOR FRAMING, DECKING OR
 FINISH MATERIAL NOR FLOOR DRAIN MATERIAL? 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) THE PLANS INDICATE THIS IS A NEW BREWERY BUT THE
 PLANS ARE SILENT AS TO THE ALCOHOL CONTENT. PLEASE NOTE
 WHEN THE BEVERAGES HAVE AN ALCOHOL CONTENT OF OVER 16
 PER CENT THEN THE BREWERY WOULD BE CLASSIFIED AS AN F1
 OCCUPANCY AND OCCUPANCY SEPARATION MAY BE REQUIRED. SEE
 FBC-B TABLE 508.4. ONE HOUR REDUCTION FOR SPRINKLERED
 BUILDINGS.
  
 5) QUESTION, DOESN?T ALL BREWERIES REQUIRE A BOILER AND
 1 HOUR RATED ROOM. THE PLANS DO NOT SHOW THE BOILER NOR
 SIZE? PLEASE REVIEW THE 2014 FBC-B TABLE 509. ROOMS
 WITH BOILERS WHERE THE LARGEST PIECE OF EQUIPMENT IS
 OVER 15 PSI AND 10 HORSEPOWER WOULD REQUIRE 1 HOUR
 SEPARATION OR AUTOMATIC SPRINKLERS SYSTEM.
  
 6) SHEETS A.1 AND A3.0 BOTH SHOW A NEW BAR SYSTEM ON
 THE EAST SIDE OF THE BUILDING. PLEASE PROVIDE A WALL
 DETAIL OF THE INFILL WALL AND DOOR/ WINDOW SYSTEM.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1. COMMERCIAL BUILDINGS: BUILDING.
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 BUILDING ENVELOPE
 WIND REQUIREMENTS
  
 7) MISSING THE WIND DESIGN. PLEASE NOTE THE NEGATIVE
 PRESSURES ARE TAKEN FROM THE ROOF.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 8) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,
 (B) WINDOWS
 ( C ) MECHANICAL EQUIPMENT STAND WALL MOUNT
  
 9) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) SHEET A1.0 INDICATES THERE ARE 180 INDOOR SEATS AND
 THE PLAN SHOWS 84 EXTERIOR SEATS WITH A TOTAL
 264 SEATS. THE ACCESSIBILITY CODE REQUIRES 0.05 % OF
 ALL SEATING TO BE ACCESSIBLE. 13.2 OR 14 SEATS ALWAYS
 ROUND UP. 226.1 WHERE DINING SURFACES ARE PROVIDED FOR
 THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF
 THE SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 11) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 12) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 INCLUDING THE EXTERIOR BAR, TABLES, LUNCH COUNTERS, AND
 BOOTHS.
  
 13)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 13)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 14) SHEET A2.1 THE UPSTAIRS SHOWS A NEW FIRE RATED EXIT
 DOOR. NO NOTATION AS TO THE SIZE OF DOOR OR HARDWARE
 FOR THE FIRE RATED DOOR.
  
 14A) 2014 FBC-B TABLE 716.5 OPENING PROTECTIVES.
  
 14B) 2014 FBC-B 1008.1.1 SIZE OF DOORS. THE MINIMUM
 WIDTH OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE
 OCCUPANT LOAD THEREOF AND SHALL PROVIDE A CLEAR WIDTH
 OF 32 INCHES (813 MM). CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 14C) 2014 FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF
 50 OR MORE IN A GROUP A OCCUPANCY SHALL NOT BE PROVIDED
 WITH A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  