| 2020-02-27 07:10:34 | PLUMBING 2ND REVIEW**DENIED**17121018*8 |
| | ONLY 7 OF THE 16 PLUMBING COMMENTS HAVE BEEN ADDRESSED |
| | DURING THIS 2ND PLAN SUBMITTAL. IF THESE REMAINING 9 |
| | COMMENTS ARE NOT COMPLETELY ADDRESSED A 4X PLAN REVIEW |
| | FEE COULD BE ASSESSED PER FL STATE STATUTE |
| | 553.80?ENFORCEMENT.?2(B)?WITH RESPECT TO EVALUATION OF |
| | DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT |
| | FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH |
| | THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| | REVIEW. |
| | |
| | COMMENTS STILL OUTSTANDING: |
| | 1) PROVIDE COMPLETE INSTALLATION MANUAL/ SPECS FOR THE |
| | GREASE INTERCEPTOR, DOMESTIC BOOSTER PUMPS, AND WATER |
| | HEATERS. FBC 107.2.1 |
| | 2) SHT. P1.01 WATER HEATER CALLS OUT BTU RATING AS 700K |
| | BTU BUT UNDER HEATER DETAIL LIST THEN AS 800K BTU WHILE |
| | SHT. P11 SAYS NO GAS ON THIS PROJECT. PLEASE CLARIFY |
| | FBC 107.2.1 |
| | 3) PROVIDE ANTI-SIPHONING BACKFLOW DEVICE FOR THE HOT |
| | WATER STORAGE TANKS SHOWN ON SHT. P1.01. FBC-PLB 608.2 |
| | 4) PROVIDE MEANS OF THERMO EXPANSION FOR THE HOT WATER |
| | SYSTEM. FBC-PLB 607.3 |
| | 5) SHT. L1-1 LIST THE BACKFLOW FOR THE IRRIGATION |
| | SYSTEM A WILKINS 720A PVB. THIS WILKINS DEVICE IS NOT |
| | LEAD FREE/ NS61 APPROVED OR RPZ. PVB?S ARE NOT |
| | PERMITTED ON COMMERCIAL PROPERTIES WHILE BEING CONNECT |
| | TO AN INDEPENDENT WATER METER. WPB CROSS CONNECTION |
| | MANUAL 2017 |
| | 6) PROVIDE A COMPLETE SANITARY, DOMESTIC WATER, STORM |
| | WATER, AND GREASE WASTE ISOMETRIC DRAWING FROM THE |
| | GROUND FLOOR TO THE 4TH. FBC 107.3.5 |
| | 7) PROVIDE HOW YOU SIZED THE GREASE INTERCEPTOR AND |
| | WHICH METHOD YOU ARE USING. FBC-PLB 1003 |
| | 8) SHT. P1.00 SHOWS THE KITCHEN DISCHARGING INTO THE |
| | SANITARY SEWER AND NOT THE GREASE. BEING THAT COOKING |
| | WILL BE DONE HERE IT MUST GO THOUGH THE GREASE |
| | INTERCEPTOR. FBC-PLB 1003.1 |
| | 9) PROVIDE DETAIL ON ELEVATOR SUMP PUMP IS CONNECTING |
| | INTO THE SANITARY SYSTEM. FBC 107.3.5 |
| | |
| | NEW COMMENTS BASE ON NEW SHEETS SUBMITTED: |
| | 10) YOU CALL OUT TO SEE OWNERS RESPONSE LETTER BUT ONE |
| | COULD NOT BE LOCATED IN RESPONSE #1. PLEASE PROVIDE. |
| | PLEASE REMOVE THE WORDING EXTENDED STAY ROOMS AS THIS |
| | THE TERM USED FOR STAYS OR 30 DAYS. FBC 107.2.1 |
| | 11) IN YOUR RESPONSE LETTER IT JUMPS FROM 5 TO 7 AND 6 |
| | IS MISSING. PLEASE CLARIFY. FBC 107.2.1 |
| | 12) SHT. A 7.02 DETAIL #7 THE TOILET PAPER HOLDER PER |
| | FBC-ACC 604.7 MUST BE 7?-9? FROM THE FRONT LIP OF THE |
| | TOILET TO THE CENTER OF WHERE IT DISPENSES PAPER FROM. |
| | 13) THE ACCESSIBLE WASHER AND DRYERS AS SHOWN I DO NOT |
| | FEEL COMPLY. BEING A STACKABLE UNIT IT WOULD NOT MEET |
| | THE REQUIRED REACH RANGES. THE PARALLEL CLEAR FLOOR |
| | SPACE ACCESS TO THE UNITS IS BEING BLOCKED BY THE |
| | CLOSET WALLS.PLEASE CLARIFY AND SHOW DETAIL SHOWING HOW |
| | THIS DESIGN COMPLIES. FBC-ACC 611.2, 611.4 |
| | 14) SHT A 7.02 DETAIL # 11. THE SHOWER PAN DETAIL IS |
| | MISSING THE REQUIRED 2% PRE-PITCH UNDER THE PAN. |
| | FBC-PLB 717.5.2 |
| | 15) SHT. A 7.02 DETAIL # 7 PLEASE SHOW THE GRAB BAR IS |
| | MOUNTED 12? FROM THE TOILET CENTERLINE TOWARDS THE WALL |
| | AS SHOWN IN FBC-ACC 604.5.2 |
| | 16) SHT. 7.02 DETAIL 8 THE ACCESSIBLE SHOWERS ARE SHOWN |
| | WITH A CURB. THE MAX ALLOWED THRESHOLD IS ??FBC-ACC |
| | 608.7 |
| | |
| | TIM HUNT |
| | PLUMBING PLAN REVIEW |
| | CITY OF WEST PALM BEACH (CGA SOLUTIONS) |
| | 561-248-2703 |
| | [email protected] |
| | |
| | |