| 2020-01-13 12:54:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 2.01, A 5.00 & FP 2.00 - THERE APPEARS TO BE |
| | AN OPEN RAILING ALONG THE MEZZANINE LEVEL CREATING AN |
| | ATRIUM WITH NO PROTECTION. |
| | |
| | PER NFPA 101, CH 8 |
| | |
| | 8.6.7* ATRIUMS. UNLESS PROHIBITED BY CHAPTERS 11 |
| | THROUGH 43, AN |
| | ATRIUM SHALL BE PERMITTED, PROVIDED THAT ALL OF THE |
| | FOLLOWING |
| | CONDITIONS ARE MET: |
| | |
| | (1) THE ATRIUM IS SEPARATED FROM THE ADJACENT SPACES BY |
| | FIRE |
| | BARRIERS WITH NOT LESS THAN A 1-HOUR FIRE RESISTANCE |
| | RATING, |
| | WITH OPENING PROTECTIVES FOR CORRIDOR WALLS, UNLESS ONE |
| | OF THE |
| | FOLLOWING IS MET: |
| | (A) THE REQUIREMENT OF 8.6.7(1) SHALL NOT APPLY TO |
| | EXISTING, |
| | PREVIOUSLY APPROVED ATRIUMS. |
| | (B) ANY NUMBER OF LEVELS OF THE BUILDING SHALL BE |
| | PERMITTED |
| | TO OPEN DIRECTLY TO THE ATRIUM WITHOUT ENCLOSURE, BASED |
| | ON THE RESULTS OF THE ENGINEERING ANALYSIS REQUIRED IN |
| | 8.6.7(5). |
| | (C)* GLASS WALLS AND INOPERABLE WINDOWS SHALL BE |
| | PERMITTED |
| | IN LIEU OF THE FIRE BARRIERS WHERE ALL THE FOLLOWING |
| | ARE |
| | MET: |
| | I. AUTOMATIC SPRINKLERS ARE SPACED ALONG BOTH SIDES |
| | OF THE GLASS WALL AND THE INOPERABLE WINDOWS AT |
| | INTERVALS NOT TO EXCEED 6 FT (1830 MM). |
| | II. THE AUTOMATIC SPRINKLERS SPECIFIED IN 8.6.7(C)I ARE |
| | LOCATED AT A DISTANCE FROM THE GLASS WALL NOT TO |
| | EXCEED 12 IN. (305 MM) AND ARRANGED SO THAT THE |
| | ENTIRE SURFACE OF THE GLASS IS WET UPON OPERATION OF |
| | THE SPRINKLERS. |
| | III. THE GLASS WALL IS OF TEMPERED, WIRED, OR LAMINATED |
| | GLASS HELD IN PLACE BY A GASKET SYSTEM THAT ALLOWS |
| | THE GLASS FRAMING SYSTEM TO DEFLECT WITHOUT |
| | BREAKING (LOADING) THE GLASS BEFORE THE SPRINKLERS |
| | OPERATE. |
| | IV. THE AUTOMATIC SPRINKLERS REQUIRED BY 8.6.7(C)I ARE |
| | NOT REQUIRED ON THE ATRIUM SIDE OF THE GLASS WALL |
| | AND THE INOPERABLE WINDOW WHERE THERE IS NO |
| | WALKWAY OR OTHER FLOOR AREA ON THE ATRIUM SIDE ABOVE |
| | THE MAIN FLOOR LEVEL. |
| | V. DOORS IN THE GLASS WALLS OF GLASS OR OTHER MATERILA |
| | THAT RESISTS PASSAGE OF SMOKE. |
| | VI. DOORS IN THE GLASS WALLS ARE SELF-CLOSING OR |
| | AUTOMATIC-CLOSING UPON DETECTION OF SMOKE. |
| | VII. THE GLASS IS CONTINUOUS VERTICALLY, WITHOUT |
| | HORIZONTAL MULLIONS, WINDOW TREATMENTS, OR OTHER |
| | OBSTRUCTIONS THAT WOULD INTERFERE WITH THE WETTING |
| | OF THE ENTIRE GLASS SURFACE. |
| | (2) ACCESS TO EXITS IS PERMITTED TO BE WITHIN THE |
| | ATRIUM, AND EXIT |
| | DISCHARGE IN ACCORDANCE WITH 7.7.2 IS PERMITTED TO BE |
| | WITHIN |
| | THE ATRIUM. |
| | (3) THE OCCUPANCY WITHIN THE ATRIUM MEETS THE |
| | SPECIFICATIONS FOR |
| | CLASSIFICATION AS LOW OR ORDINARY HAZARD CONTENTS. (SEE |
| | 6.2.2.) |
| | (4) THE ENTIRE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH |
| | SECTION 9.7 |
| | (5) *FOR OTHER THAN EXISTING, PREVIOUSLY APPROVED |
| | ATRIUMS, AN |
| | ENGINEERING ANALYSIS IS PERFORMED THAT DEMONSTRATES |
| | THAT THE |
| | BUILDING IS DESIGNED TO KEEP THE SMOKE LAYER INTERFACE |
| | ABOVE THE |
| | HIGHEST UNPROTECTED OPENING TO ADJOINING SPACES, OR 6 |
| | FT (1830 |
| | MM) ABOVE THE HIGHEST FLOOR LEVEL OF EXIT ACCESS OPEN |
| | TO THE |
| | ATRIUM, FOR A PERIOD EQUAL TO 1.5 TIMES THE CALCULATED |
| | EGRESS TIME |
| | OR 20 MINUTES, WHICHEVER IS GREATER. |
| | (6) *FOR OTHER THAN EXISTING, PREVIOUSLY APPROVED SMOKE |
| | CONTROL |
| | SYSTEMS, WHERE AN ENGINEERED SMOKE CONTROL SYSTEM IS |
| | INSTALLED TO MEET THE REQUIREMENTS OF 8.6.7, THE SYSTEM |
| | IS |
| | INDEPENDENTLY ACTIVATED BY EACH OF THE FOLLOWING: |
| | (A) UPON ACTUATION OF THE REQUIRED AUTOMATIC SPRINKLER |
| | SYSTEM |
| | WITHIN THE ATRIUM OR AREAS OPEN TO THE ATRIUM |
| | (B) MANUAL CONTROLS THAT ARE READILY ACCESSIBLE TO THE |
| | FIRE |
| | DEPARTMENT |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE WITH CODE. |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |