| 2019-03-04 10:56:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A 2.01 - THERE IS AN INDICATION OF AN EMEGENCY |
| | GENERATOR. THE GENERATOR INSTALLATION SHALL BE UNDER |
| | SEPARATE SHOP DRAWINGS AND PERMIT. |
| | |
| | THE GENRATOR INSTALL SHALL ALSO COMPLY WITH THE |
| | REQUIRMENTS OF NFPA 110, TO INCLUDE TYPE |
| | |
| | PER NFPA 110 |
| | |
| | CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY |
| | SYSTEMS (EPSSS) |
| | 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF |
| | ELECTRICAL |
| | POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO |
| | LOADS FOR |
| | A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND |
| | WITHIN A SPECIFIED |
| | TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER |
| | SUPPLY |
| | AS SPECIFIED IN TABLE 4.1(B). |
| | |
| | 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN |
| | HOURS, FOR |
| | WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD |
| | WITHOUT |
| | BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).] |
| | 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN |
| | SECONDS, |
| | THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE |
| | TRANSFER |
| | SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE |
| | 4.1(B) |
| | PROVIDES THE TYPES DEFINED BY THIS STANDARD. |
| | 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF |
| | EQUIPMENT |
| | INSTALLATION, PERFORMANCE, AND MAINTENANCE. |
| | 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| | OF THE |
| | EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE |
| | OR |
| | SERIOUS INJURIES. |
| | 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| | OF THE |
| | EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND |
| | SAFETY. |
| | 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED. |
| | 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT |
| | ALL LOADS |
| | SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER |
| | THAT |
| | MEETS ALL THE FOLLOWING CRITERIA: |
| | (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE |
| | LOAD |
| | (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED |
| | IN TABLE |
| | 4.1(A) |
| | (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED |
| | IN TABLE |
| | 4.1(B) |
| | |
| | PLEASE PROVIDE THE CLASSIFICATION, TYPE AND LEVEL ON |
| | THIS MASTER PLAN AND AN APPLICABLE NOTE FOR SHOP |
| | DRAWINGS. |
| | |
| | |
| | 1A) SHEET M1.0A - THERE ARE NO FIRE CODE REFERENCES FOR |
| | REVIEW OR COMPLIANCE. THE INSTALLATION SHALL COMPLY |
| | WITH NFPA 110, STANDARD FOR |
| | EMERGENCY AND STANDBY POWER SYSTEMS, 2013 EDITION |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN |
| | APPLICABLE NOTE ACKNOWLEDGMENT OF THE ABOVE CODE. |
| | |
| | |
| | |
| | |
| | |
| | 2) SHEET A 2.01 - THE VENTILATION/EXHAUST SYSTEMS ARE |
| | INDCATED WITH OPENINGS THAT MAY IN CONFLICT WITH THE |
| | REQUIREMENTS PER ABOVE. |
| | |
| | |
| | 7.7 HEATING, COOLING, AND VENTILATING. |
| | 7.7.1* WITH THE EPS RUNNING AT RATED LOAD, VENTILATION |
| | AIRFLOW |
| | SHALL BE PROVIDED TO LIMIT THE MAXIMUM AIR TEMPERATURE |
| | IN THE |
| | EPS ROOM OR THE ENCLOSURE HOUSING THE UNIT TO THE |
| | MAXIMUM |
| | AMBIENT AIR TEMPERATURE REQUIRED BY THE EPS |
| | MANUFACTURER. |
| | 7.7.1.1 CONSIDERATION SHALL BE GIVEN TO ALL THE HEAT |
| | EMITTED TO |
| | THE EPS EQUIPMENT ROOM BY THE ENERGY CONVERTER, |
| | UNINSULATED |
| | OR INSULATED EXHAUST PIPES, AND OTHER HEAT-PRODUCING |
| | EQUIPMENT. |
| | 7.7.2 AIR SHALL BE SUPPLIED TO THE EPS EQUIPMENT FOR |
| | COMBUSTION. |
| | 7.7.2.1* FOR EPS SUPPLYING LEVEL 1 EPSS, VENTILATION |
| | AIR SHALL |
| | BE SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE THE BUILDING |
| | BY AN |
| | EXTERIOR WALL OPENING OR FROM A SOURCE OUTSIDE THE |
| | BUILDING BY |
| | A 2-HOUR FIRE-RATED AIR TRANSFER SYSTEM. |
| | 7.7.2.2 FOR EPS SUPPLYING LEVEL 1 EPSS, DISCHARGE AIR |
| | SHALL BE |
| | DIRECTED OUTSIDE THE BUILDING BY AN EXTERIOR WALL |
| | OPENING OR TO |
| | AN EXTERIOR OPENING BY A 2-HOUR FIRE-RATED AIR TRANSFER |
| | SYSTEM. |
| | 7.7.2.3 FIRE DAMPERS, SHUTTERS, OR OTHER SELF-CLOSING |
| | DEVICES SHALL |
| | NOT BE PERMITTED IN VENTILATION OPENINGS OR DUCTWORK |
| | FOR SUPPLY |
| | OR RETURN/DISCHARGE AIR TO EPS EQUIPMENT FOR LEVEL 1 |
| | EPSS. |
| | 7.7.3 VENTILATION AIR SUPPLY SHALL BE FROM OUTDOORS OR |
| | FROM A |
| | SOURCE OUTSIDE THE BUILDING BY AN EXTERIOR WALL OPENING |
| | OR |
| | FROM A SOURCE OUTSIDE THE BUILDING BY A 2-HOUR |
| | FIRE-RATED AIR |
| | TRANSFER SYSTEM. |
| | 7.7.4 VENTILATION AIR SHALL BE PROVIDED TO SUPPLY AND |
| | DISCHARGE |
| | COOLING AIR FOR RADIATOR COOLING OF THE EPS WHEN |
| | RUNNING |
| | AT RATED LOAD. |
| | 7.7.4.1 VENTILATION AIR SUPPLY AND DISCHARGE FOR |
| | RADIATORCOOLED |
| | EPS SHALL HAVE A MAXIMUM STATIC RESTRICTION OF 125 PA |
| | (0.5 IN. OF WATER COLUMN) IN THE DISCHARGE DUCT AT THE |
| | RADIATOR |
| | OUTLET. |
| | 7.7.4.2 RADIATOR AIR DISCHARGE SHALL BE DUCTED OUTDOORS |
| | OR TO |
| | AN EXTERIOR OPENING BY A 2-HOUR RATED AIR TRANSFER |
| | SYSTEM. |
| | 7.7.5 MOTOR-OPERATED DAMPERS, WHEN USED, SHALL BE |
| | SPRING |
| | OPERATED TO OPEN AND MOTOR CLOSED. FIRE DAMPERS, |
| | SHUTTERS, OR |
| | OTHER SELF-CLOSING DEVICES SHALL NOT BE PERMITTED IN |
| | VENTILATION |
| | OPENINGS OR DUCTWORK FOR SUPPLY OR RETURN/DISCHARGE AIR |
| | TO |
| | EPS EQUIPMENT FOR LEVEL 1 EPSS. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND OR CORRECT AS |
| | APPLICABLE. |
| | |
| | |
| | |
| | 3) SHEET A 2.01 - THERE IS AN OVERHEAD DOOR INDICATED |
| | IN A 2 HOUR FIRE WALL AT THE STORAGE GARBAGGE ROOM. |
| | |
| | THERE IS NO FIRE RATING INDICATED ON THE DOOR SCHEDULE. |
| | |
| | ADDITIONALLY, WILL THIS DOOR BE ON A FUSIBLE LINK? |
| | |
| | PLEASE REVIEW AND CORRECT AND PROVIDE DETAILS. |
| | |
| | |
| | |
| | |
| | 4) SHEET A 2.01 - THE EXITING FROM THE GENERATOR ROOM |
| | INDICATES PASSAGE ALONG A 2 HOUR WALL; HOWEVER, THERE |
| | IS A LOUVER INDICATED AT THAT WALL AREA. |
| | |
| | THE PATH OF TRAVEL IS REQUIRED TO BE PROTECTED PER NFPA |
| | 101, CHAPTER 8 FEATURES OF FIRE PROTECTION |
| | |
| | 8.3.1.2* FIRE BARRIERS SHALL COMPLY WITH ONE OF THE |
| | FOLLOWING: |
| | (1) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL |
| | TO OUTSIDE WALL |
| | OR FROM ONE FIRE BARRIER TO ANOTHER, OR A COMBINATION |
| | THEREOF, |
| | INCLUDING CONTINUITY THROUGH ALL CONCEALED SPACES, SUCH |
| | AS THOSE |
| | FOUND ABOVE A CEILING, INCLUDING INTERSTITIAL SPACES. |
| | (2) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL |
| | TO OUTSIDE WALL |
| | OR FROM ONE FIRE BARRIER TO ANOTHER, AND FROM THE FLOOR |
| | TO THE |
| | BOTTOM OF THE INTERSTITIAL SPACE, PROVIDED THAT THE |
| | CONSTRUCTION |
| | ASSEMBLY FORMING THE BOTTOM OF THE INTERSTITIAL SPACE |
| | HAS A FIRE |
| | RESISTANCE RATING NOT LESS THAN THAT OF THE FIRE |
| | BARRIER. |
| | 8.3.1.3 WALLS USED AS FIRE BARRIERS SHALL COMPLY WITH |
| | CHAPTER 7 OF |
| | NFPA 221, STANDARD FOR HIGH CHALLENGE FIRE WALLS, FIRE |
| | WALLS, AND |
| | FIRE BARRIER WALLS. THE NFPA 221 LIMITATION ON |
| | PERCENTAGE WIDTH OF |
| | OPENINGS SHALL NOT APPLY. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES AND NARRATIVE. |
| | |
| | |
| | |
| | 5) SHEET A 2.01 - THERE IS AN INDICATION OF A EXIT FROM |
| | THE GARAGE AREA PASSING BY A BOILER ROOM. |
| | |
| | 28.3.2 PROTECTION FROM HAZARDS. |
| | 28.3.2.1 GENERAL. ALL ROOMS CONTAINING HIGH-PRESSURE |
| | BOILERS, |
| | REFRIGERATING MACHINERY, TRANSFORMERS, OR OTHER SERVICE |
| | EQUIPMENT |
| | SUBJECT TO POSSIBLE EXPLOSION SHALL NOT BE LOCATED |
| | DIRECTLY UNDER OR |
| | DIRECTLY ADJACENT TO EXITS AND SHALL BE EFFECTIVELY CUT |
| | OFF FROM |
| | OTHER PARTS OF THE BUILDING AS SPECIFIED IN SECTION |
| | 8.7. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES AND NARRATIVE |
| | |
| | |
| | |
| | 6) SHEET A 9.0 - THERE IS AN INDICATION OF A FP&L VAULT |
| | BOX DIRECTLY BESIDE AN EXIT FROM STAIRWAY, ST 1. |
| | |
| | 28.3.2 PROTECTION FROM HAZARDS. |
| | 28.3.2.1 GENERAL. ALL ROOMS CONTAINING HIGH-PRESSURE |
| | BOILERS, |
| | REFRIGERATING MACHINERY, TRANSFORMERS, OR OTHER SERVICE |
| | EQUIPMENT |
| | SUBJECT TO POSSIBLE EXPLOSION SHALL NOT BE LOCATED |
| | DIRECTLY UNDER OR |
| | DIRECTLY ADJACENT TO EXITS AND SHALL BE EFFECTIVELY CUT |
| | OFF FROM |
| | OTHER PARTS OF THE BUILDING AS SPECIFIED IN SECTION |
| | 8.7. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES AND NARRATIVE |
| | |
| | |
| | |
| | |
| | 7) SHEET A 9.0 - THERE ARE DOORS THAT APPEAR TO OPEN |
| | AND ENCROACH MORE THAN ONE HALF THE REQUIRED EGRESS |
| | WIDTH; LUGGAGE ROOM, CONFERENCE SITTING AREA CORRIDOR |
| | (3), THE EXIT DOOR AT ST 4, |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.2.1.4.3* DOOR LEAF ENCROACHMENT. |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS |
| | SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED |
| | WIDTH OF AN AISLE, |
| | A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, |
| | UNLESS BOTH |
| | OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING |
| | BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF |
| | 7.2.1.4.3.2. |
| | |
| | |
| | |
| | |
| | 8) SHEET A 2.01 & A 2.03 - THERE APPEARS TO BE STOVE |
| | TOPS INDICATED WITH THE KITCHENETTE AND BREAK ROOM. |
| | |
| | ANY KITCHEN EQUIPMENT WITHIN THESE ROOMS SHALL BE |
| | PROTECTED PER NFPA 101 & 96 WITH ALL APPLICABLE HOODS |
| | AND SUPPRESSION SYSTEMS UNDER SEPARATE SHOP DRAWINGS. |
| | |
| | PER NFPA 1 CH 50 & 101 CH 9: |
| | |
| | 50.1.1 THE DESIGN, INSTALLATION, OPERATION, INSPECTION |
| | AND MAINTENANCE OF ALL PUBLIC AND PRIVATE COMMERCIAL |
| | COOKING |
| | EQUIPMENT SHALL COMPLY WITH THIS CHAPTER AND NFPA 96, |
| | STANDARD |
| | FOR VENTILATION CONTROL AND FIRE PROTECTION OF |
| | COMMERCIAL COOKING OPERATIONS. |
| | |
| | 50.1.2 THIS CHAPTER SHALL APPLY TO RESIDENTIAL COOKING |
| | EQUIPMENT |
| | USED FOR COMMERCIAL COOKING OPERATIONS. [96:1.1.2] |
| | |
| | 50.2 GENERAL REQUIREMENTS. |
| | 50.2.1 GENERAL. |
| | 50.2.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING |
| | SMOKE |
| | OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN |
| | EXHAUST SYSTEM |
| | THAT COMPLIES WITH ALL THE EQUIPMENT AND PERFORMANCE |
| | REQUIREMENTS OF THIS CHAPTER. [96:4.1.1] |
| | |
| | 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY |
| | ANOTHER |
| | SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS |
| | SHALL BE PROTECTED |
| | IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION |
| | CONTROL AND |
| | FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS, |
| | UNLESS SUCH |
| | INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| | WHICH SHALL BE |
| | PERMITTED TO BE CONTINUED IN SERVICE. |
| | |
| | PLEASE REVIEW AND CORRECT AND PROVIDE AN APPLICABLE |
| | NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 9) SHEET A 2.01 - THERE ARE ELEVATORS INDICATED. |
| | |
| | PER NFPA 101 CH 28 - |
| | |
| | 28.5.3 ELEVATORS, ESCALATORS, AND CONVEYORS. |
| | 28.5.3.1 ELEVATORS, ESCALATORS, AND CONVEYORS SHALL |
| | COMPLY WITH |
| | THE PROVISIONS OF SECTION 9.4. |
| | 28.5.3.2* IN HIGH-RISE BUILDINGS, ONE ELEVATOR SHALL BE |
| | PROVIDED |
| | WITH A PROTECTED POWER SUPPLY AND SHALL BE AVAILABLE |
| | FOR USE BY |
| | THE FIRE DEPARTMENT IN CASE OF EMERGENCY. |
| | |
| | |
| | WHICH OF THE ELEVATORS MEET THE REQUIREMENTS? |
| | |
| | |
| | |
| | |
| | 10) SHEET 2.01 - THERE ARE ELEVATORS INDICATED. |
| | |
| | PER THE STATE OF FLORIDA CHAPTER 399 FLORIDA STATUTES. |
| | SECTION 399.15, SECTION 17: |
| | REGIONAL EMERGENCY ELEVATOR ACCESS ? |
| | (1) IN ORDER TO PROVIDE EMERGENCY ACCESS TO ELEVATORS: |
| | (A) FOR EACH BUILDING IN THIS STATE WHICH IS SIX OR |
| | MORE STORIES IN HEIGHT, INCLUDING, BUT NOT LIMITED TO, |
| | HOTELS AND CONDOMINIUMS, |
| | ON WHICH A BUILDING PERMIT IS ISSUED AFTER SEPTEMBER |
| | 30, 2006, ALL OF THE KEYS FOR ELEVATORS THAT ALLOW |
| | PUBLIC ACCESS, INCLUDING, |
| | BUT NOT LIMITED TO, SERVICE AND FREIGHT ELEVATORS, MUST |
| | BE KEYED SO AS TO ALLOW ALL ELEVATORS WITHIN EACH OF |
| | THE SEVEN STATE |
| | EMERGENCY RESPONSE REGIONS TO OPERATE IN FIRE EMERGENCY |
| | SITUATIONS WITH ONE MASTER ELEVATOR KEY. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN |
| | APPLICABLE NOTE OF ACKNOWLEDGEMENT |
| | |
| | |
| | |
| | |
| | |
| | 11) SHEET FP 1.00 - THERE ARE INDICATIONS OF SIDEWALL |
| | SPRINKLER HEADS AT THE BOTTOM OF HOISTWAYS. |
| | |
| | PER NFPA 13 |
| | |
| | 8.15.5 ELEVATOR HOISTWAYS AND MACHINE ROOMS. |
| | |
| | 8.15.5.2 THE SPRINKLER REQUIRED AT THE BOTTOM OF THE |
| | ELEVATOR |
| | HOISTWAY BY 8.15.5.1 SHALL NOT BE REQUIRED FOR |
| | ENCLOSED, NONCOMBUSTIBLE |
| | ELEVATOR SHAFTS THAT DO NOT CONTAIN COMBUSTIBLE |
| | HYDRAULIC FLUIDS. |
| | |
| | PLEASE REVIEW AND CORRECT AND IF APPLICABLE THE |
| | SPRINKLER HEAD MAY BE REMOVED. |
| | |
| | |
| | |
| | 12) SHEET FP 1.00 - THERE DOES NOT APPEAR TO BE A |
| | SPRINKLER HEAD IN THE SERVICE SINK ROOM. |
| | |
| | PER NFPA 101 TOTAL FIRE SPRINKLER COVERAGE IS REQUIRED. |
| | |
| | 28.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| | AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE |
| | WITH 28.3.5.3. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 13) SHEET FP 2.00 - THERE DOES NOT APPEAR TO BE A |
| | SPRINKLER HEAD IN THE SERVICE SINK ROOM. |
| | |
| | PER NFPA 101 TOTAL FIRE SPRINKLER COVERAGE IS REQUIRED. |
| | |
| | 28.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| | AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE |
| | WITH 28.3.5.3. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 14) SHEET FP 3.00 - THERE DOES NOT APPEAR TO BE A |
| | SPRINKLER HEAD IN THE SERVICE SINK ROOM. |
| | |
| | PER NFPA 101 TOTAL FIRE SPRINKLER COVERAGE IS REQUIRED. |
| | |
| | 28.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| | AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE |
| | WITH 28.3.5.3. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 15) SHEET FP 4.00 - THERE IS A SPRINKLER HEAD NEAR ST 2 |
| | IN THE CORRIDOR AT THE CORRIDOR DOOR THAT APPEARS TO BE |
| | WITHIN THE WALL. |
| | |
| | ADDITIONALLY, THIS SHEET MAY BE INCORRECTLY LABLED AND |
| | NEED CORRECTION, SE BELOW. |
| | |
| | PLEASE REVIEW AND CORRECT THE LOCATION. |
| | |
| | |
| | |
| | |
| | 16) SHEET FP 5.00 - THIS SHEET IS INDICATED AS 4TH THRU |
| | 6TH FLOORS; HOWEVER, IT SHOWS THE ROOF. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 17) SHEET FP 4.00 - THERE IS AN INDICATION OF A |
| | SPRINKLER HEAD AT THE TOP OF THE ELEVATOR HOISTWAYS. |
| | |
| | PER NFPA 13 |
| | |
| | 8.15.5.5* UPRIGHT, PENDENT, OR SIDEWALL SPRAY |
| | SPRINKLERS SHALL |
| | BE INSTALLED AT THE TOP OF ELEVATOR HOISTWAYS. |
| | 8.15.5.6 THE SPRINKLER REQUIRED AT THE TOP OF THE |
| | ELEVATOR HOISTWAY |
| | BY 8.15.5.5 SHALL NOT BE REQUIRED WHERE THE HOISTWAY |
| | FOR PASSENGER |
| | ELEVATORS IS NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE AND |
| | THE CAR ENCLOSURE MATERIALS MEET THE REQUIREMENTS OF |
| | ASME |
| | A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS. |
| | |
| | PLEASE REVIEW AND REMOVE IF APPLICABLE. |
| | |
| | |
| | |
| | 18) SHEET FP 1.00 - THERE IS A INDICATION AT NOTE 1 |
| | THAT A SPRINKLER HEAD AT BENEATH OF STAIRWAY. |
| | |
| | PER NFPA 13 |
| | |
| | 8.15.3.2.3.1 SPRINKLERS SHALL BE PERMITTED TO BE |
| | OMITTED FROM |
| | THE BOTTOM OF THE STAIRWELL WHEN THE SPACE UNDER THE |
| | STAIRS AT |
| | THE BOTTOM IS BLOCKED OFF SO THAT STORAGE CANNOT OCCUR. |
| | |
| | PLEASE REVIEW AND CORRECT IF APPLICABLE AND PROVIDE FOR |
| | BLOCKING AREA. |
| | |
| | |
| | |
| | 19) SHEET FP 9.00 - THERE ARE INDICATIONS OF FIRE LINE |
| | UNDERGROUND. |
| | |
| | ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED, TESTED |
| | AND INSPECTED UNDER SEPARATE SHOP DRAWINGS AND PERMIT. |
| | |
| | FIRE LINE UNDERGROUND SHALL BE INSTALLED, TESTED AND |
| | INSPECTED PER NFPA 24, |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | |
| | 20) THERE DOES NOT APPEAR TO BE ANY CLEAR INFORMATION |
| | INDICATED FOR SMOKE CONTROL. |
| | |
| | PLEASE PROVIDE A DETAILED RATIONAL ANALYSIS INCL;UDING |
| | SEQUENCE OF OPERATION REGARDING SMOKE CONTROL FOR THIS |
| | PROJECT. |
| | |
| | |
| | |
| | |
| | 21) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 22) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |