| 2018-01-08 12:21:32 | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| | NFPA 70 2011 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | |
| | C405.2.5 EXTERIOR LIGHTING CONTROLS. |
| | |
| | LIGHTING FOR EXTERIOR APPLICATIONS OTHER THAN EMERGENCY |
| | LIGHTING THAT IS INTENDED TO BE AUTOMATICALLY OFF |
| | DURING BUILDING OPERATION, LIGHTING SPECIFICALLY |
| | REQUIRED TO MEET HEALTH AND LIFE SAFETY REQUIREMENTS OR |
| | DECORATIVE GAS LIGHTING SYSTEMS SHALL: |
| | |
| | 1.BE PROVIDED WITH A CONTROL THAT AUTOMATICALLY TURNS |
| | OFF THE LIGHTING AS A FUNCTION OF AVAILABLE DAYLIGHT. |
| | |
| | 2.WHERE LIGHTING THE BUILDING FA?ADE OR LANDSCAPE, THE |
| | LIGHTING SHALL HAVE CONTROLS THAT AUTOMATICALLY SHUT |
| | OFF THE LIGHTING AS A FUNCTION OF DAWN/DUSK AND A SET |
| | OPENING AND CLOSING TIME. |
| | |
| | 3.WHERE NOT COVERED IN ITEM 2, THE LIGHTING SHALL HAVE |
| | CONTROLS CONFIGURED TO AUTOMATICALLY REDUCE THE |
| | CONNECTED LIGHTING POWER BY NOT LESS THAN 30 PERCENT |
| | FROM NOT LATER THAN MIDNIGHT TO 6 A.M., FROM ONE HOUR |
| | AFTER BUSINESS CLOSING TO ONE HOUR BEFORE BUSINESS |
| | OPENING OR DURING ANY PERIOD WHEN ACTIVITY HAS NOT BEEN |
| | DETECTED FOR A TIME OF LONGER THAN 15 MINUTES. |
| | |
| | ALL TIME SWITCHES SHALL BE ABLE TO RETAIN PROGRAMMING |
| | AND THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD |
| | OF AT LEAST 10 HOURS. |
| | |
| | EXCEPTION: LIGHTING FOR COVERED VEHICLE ENTRANCES OR |
| | EXITS FROM BUILDINGS OR PARKING STRUCTURES WHERE |
| | REQUIRED FOR SAFETY, SECURITY OR EYE ADAPTATION. |
| | |